61
Installation and Maintenance
Service Manual
(4) Malfunction of Zero-crossing Inspection Circuit Malfunction of the IDU Fan Motor U8
Main detection points:
ƽ
Instant energization afte de-energization while the capacitordischarges slowly?
ƽ
Malfunction diagnosis process:
Troubleshooting
for U8 malfunction
Turn power off
for 1minute,the
turn back on
U8 is still
displayed
The unit returns to normal.
Conclusion:U8 is displayed due
to power off/on while the
capacitor discharges slowly.
The zero-cross detection
circuit of the mainboard is
defined abnormal.Replace
the mainboard with the same
model
End
No
Yes