GREE hotovoltaic Multi VRF for North America
93
Description of each stage of debugging progress
——
Debugging code
Code meaning and operation method
Progress
LED
Code
Display status
16/error code
Display
circularly
Malfunction occurs when debugging for heating
mode.
17_ Debugging
finished
oF
ON
The entire unit has finished debugging and
under standby-by condition.
8.3 Parameters reference value for the normal operation of unit
No.
Debug item
Parameter name
Unit
Reference
1
System
parameters
ODU
parameters
Outdoor
temperature
℃
(
℉
)
——
2
Compressor
discharge temp
℃
(
℉
)
●When compressor starts, discharge
temp in cool mode is within 70~105
℃
(158~221
℉
) and at least 10
℃
(50
℉
)
higher
than
the
high
pressure
saturation temp;
●As for temp in heat mode, it is within
65~90
℃
(149~194
℉
) and at least
10
℃
(50
℉
) higher than the high
pressure saturation temp.
3
Defrosting temp
℃
(
℉
)
●In cool mode, defrosting temp is
4~10
℃
(39~50
℉
) lower than system’s
high pressure value;
●In heat mode, defrosting temp is
about 2
℃
(36
℉
) different from
system’s low pressure value.
4
System
high
pressure
℃
(
℉
)
●In cool mode, the normal high
pressure value is within 20
℃
~55
℃
(68~131
℉
). According to the change
of ambient temp and system’s
operating capacity, the high pressure
value will be 10
℃
~30
℃
(50~86
℉
)
higher than ambient temp. The higher
ambient temp is, the smaller temp
difference is. If ambient temp is
25~35
℃
(77~95
℉
) in cool mode,
system’s high pressure value will be
within 44~53
℃
(111~127
℉
).
●In heat mode, if ambient temp is
above -5
℃
(23
℉
), system’s high
pressure value is within 40~52
℃
(104~126
℉
). If ambient temp is low
Содержание GMV-Y36WL/A-T
Страница 1: ...Photovoltaic Multi VRF for North America Capacity 36 kBtu h 60 kBtu h Rated Frequency 60 Hz...
Страница 3: ...GREE Photovoltaic Multi VRF for North America 1 PRODUCT...
Страница 15: ...GREE Photovoltaic Multi VRF for North America 13 CONTROL...
Страница 18: ...GREE Photovoltaic Multi VRF for North America 16 2 Wired Controller 2 1 Control panel...
Страница 19: ...GREE Photovoltaic Multi VRF for North America 17...
Страница 20: ...GREE Photovoltaic Multi VRF for North America 18 Button Graphics...
Страница 28: ...GREE Photovoltaic Multi VRF for North America 26 4 3 2 2 Appearance...
Страница 34: ...GREE Photovoltaic Multi VRF for North America 32 Installation is in progress...
Страница 37: ...GREE Photovoltaic Multi VRF for North America 35 Installation is in progress...
Страница 39: ...GREE Photovoltaic Multi VRF for North America 37 Click Next...
Страница 57: ...GREE Photovoltaic Multi VRF for North America 55...
Страница 68: ...GREE Photovoltaic Multi VRF for North America 66 Click Get to get the current setting details of converter...
Страница 69: ...GREE Photovoltaic Multi VRF for North America 67 Switchover of Software Languages...
Страница 70: ...GREE hotovoltaic Multi VRF for North America 68 INSTALLATION...
Страница 102: ...GREE hotovoltaic Multi VRF for North America 100 MAINTENANCE...
Страница 147: ...JF00303833...