72
(5)
When the diameter of copper pipe is equal to or greater than
Φ15.9 mm, the
thickness of insulation material should be at least 20 mm; when the diameter of
copper pipe is less than 15.9 mm, the thickness of insulation material should be at
least 15 mm.
2.4 Communication cable and control cable
Note: For air conditioning units installed in places with strong electromagnetic
interference, shielded wire must be used as the communication cables of the IDU and
wired controller, and shielded twisted pairs must be used as the communication cables
between IDUs and between the IDU and ODU.
Communication cable selection for ODU and IDUs
Material Type
Total Length of
Communication Cable
between IDU Unit and
IDU (ODU ) Unit L(m/feet)
Wire size
Remarks
Light/Ordinary
polyvinyl chloride
sheathed cord.
L
≤
1000(3280-5/6)
≥2×AWG18
1) If the wire diameter is enlarged
to 2×AWG16, the total
communication line length can
reach 1500 m (4921-1/4feet).
2) The cord shall be Circular cord
(the cores shall be twisted
together).
3) If unit is installed in places with
intense magnetic field or strong
interference, it is necessary to
use shielded wire.
2.5 Power cable
Only copper conductors can be used as power cables. The copper conductors must
meet relevant national standard and satisfy the carrying capacity of unit.
2.6 Hanger rod and support
(1)
Hanger rod: M8 or M10;
(2)
U-steel: 14# or above;
(3)
Angle steel: 30mm×30mm×3mm or above;
(4)
Round steel:
Φ10mm or above
3 Installation of outdoor unit
3.1 Check before installation
(1)
Before installation, please check the power cord if it complies with the power supply
requirement on the nameplate. Make sure the power supply is safe.
(2)
This air conditioner must be properly grounded through the receptacle to avoid
electric shock. The ground wire shouldn’t be connected with gas pipe, water pipe,
lightning arrester or telephone line.
(3)
Maintain good air circulation to avoid lacking oxygen.
(4)
Read this manual carefully before installation.
Содержание GMV-Y36WL/A-T
Страница 1: ...Photovoltaic Multi VRF for North America Capacity 36 kBtu h 60 kBtu h Rated Frequency 60 Hz...
Страница 3: ...GREE Photovoltaic Multi VRF for North America 1 PRODUCT...
Страница 15: ...GREE Photovoltaic Multi VRF for North America 13 CONTROL...
Страница 18: ...GREE Photovoltaic Multi VRF for North America 16 2 Wired Controller 2 1 Control panel...
Страница 19: ...GREE Photovoltaic Multi VRF for North America 17...
Страница 20: ...GREE Photovoltaic Multi VRF for North America 18 Button Graphics...
Страница 28: ...GREE Photovoltaic Multi VRF for North America 26 4 3 2 2 Appearance...
Страница 34: ...GREE Photovoltaic Multi VRF for North America 32 Installation is in progress...
Страница 37: ...GREE Photovoltaic Multi VRF for North America 35 Installation is in progress...
Страница 39: ...GREE Photovoltaic Multi VRF for North America 37 Click Next...
Страница 57: ...GREE Photovoltaic Multi VRF for North America 55...
Страница 68: ...GREE Photovoltaic Multi VRF for North America 66 Click Get to get the current setting details of converter...
Страница 69: ...GREE Photovoltaic Multi VRF for North America 67 Switchover of Software Languages...
Страница 70: ...GREE hotovoltaic Multi VRF for North America 68 INSTALLATION...
Страница 102: ...GREE hotovoltaic Multi VRF for North America 100 MAINTENANCE...
Страница 147: ...JF00303833...