GMV DC Inverter VRF
8
(1) Use copper wire only as unit‟s power cord. Operating temperature should be within its
rated value.
(2) If the power cord is more than 15 m (49-1/4 feet) long, please increase properly the
sectional area of power cord to avoid overload, which may cause accident.
(3) Above selection requirements: Power cord size is based on BV single-core wire (2~4pc) at
40° (104°F) Cambient temperature when laying across plastic pipe. Air switch is D type and
used at 40°C (104°F). If actual installation condition varies, please lower the capacity
appropriately according to the specifications of power cord and air switch provided by
manufacturer.
(4) Install cut-off device near the unit. The minimum distance between each stage of cut-off
device should be 3 mm (1/8 inch) (The same for both indoor unit and outdoor unit).
4 Installation Instructions
4.1 Dimension Data
Fig 4.1