4.4 Condensate Removal
The drain pan has primary and secondary drain connection (Figure 8). Condensate
remov
al is performed by attaching a 3/4” PVC pipe to the evaporator coil pan and terminated in
accordance with local or state Plumbing/HVAC codes. The installation must include a “P” style
trap that is located closely to the evaporator coil. Do not over-tighten the drain connection(s) in
order to prevent possible damage to the evaporator drain pan.
See Fig 4.6 for details of a typical condensate line “P” trap.
Fig 4.4
4.5 Ductwork
This air handler is designed for a complete supply and return ductwork system.
WARNING
: Do not operate the unit without all ductwork completed.
Do not operate this product without all ductwork attached.
Inadequate ductwork that restricts airflow can result in improper performance and
compressor or heater failure. Ductwork is to be constructed in a manner that limits restrictions
and maintains suitable air velocity. Ductwork is to be sealed to the unit in a manner that will
prevent leakage.
Return Ductwork: Do not terminate the return ductwork in an area that can introduce toxic,
or objectionable fumes/odors into the ductwork. The return ductwork is to be introduced into the