GMV DC Inverter VRF
13
(
2
)
The connection of stranded wire (as shown in fig 5.1.2)
1
)
Strip about 10mm (3/8 inch) insulation of the end of stranded wire by stripping and
cutting tool.
2
)
Loosen the wiring screws on terminal board.
3
)
Insert the wire into the ring tongue terminal and tighten by crimping tool.
4
)
Use the screwdriver for tightening the terminal.
Fig 5.1-1 Fig 5.1-2
5.2 Power Cord Connection
NOTICE!
All indoor units must be unified of power supply so that they can be powered
ON/OFF at the same time.
Fig 5.2
● For units with single-phase power supply.
(
1
)
Detach the electric box lid.
(
2
)
Let the power cord pass through the wiring through-holes.
(
3
)
Connect the power cord to terminal "L, N,
".
(
4
)
Fix the power cord with wiring clamp.
5.3 Connection of Communication Wire between Indoor Unit and
Outdoor Unit (or indoor unit)
(1) Detach the electric box lid.
(2) Let the Communication cable pass through the wiring through-holes.
(3) Connect the communication wire to terminal D1 and D2 of indoor 4-bit wiring board,
as shown in fig5.3.1.