Multi Variable Air Conditioners Ducted Type Indoor Unit
10
Fig.4.3.1
4.3.2 Drainage pipe installation
(1) Insert the drain hose into the drain hole and tighten it with tapes, as shown in Fig.4.3.2. Model
with water pump will be provided with drain hose, while other models please prepare the drain
hose by yourself.
(2) Tighten the pipe clamp, with the distance between screw nut and hose smaller than 4mm.
(3) Use sealing plate to make the pipe clamp and hose insulated, as shown in Fig.4.3.3.
Fig.4.3.2
Unit: mm
Fig.4.3.3
(4) When connecting several drain pipes, follow the instruction as indicated in Fig.4.3.4. Choose
the drain collecting pipe that matches with unit capacity.
Unit: mm
Fig.4.3.4
(5) Install the trap as shown in following Fig.4.3.5.
(6) Install one trap for each unit.
(7) Convenience for cleaning trap in the future should be considered when installing it.