Multi Variable Air Conditioners Ducted Type Indoor Unit
6
3.3.2 Select Communication Line for Indoor Unit and Outdoor Unit
Fig.3.3.2
Material Type
Total Length L (m) of
Communication Cable
between Indoor Unit
and Indoor (Outdoor)
Unit
Wire size
(mm
²
)
Material
Standard
Remarks
Light/Ordinary
polyvinyl chloride
sheathed cord.
(60227 IEC 52
/60227 IEC 53)
L≤1000
≥2×0.75
IEC 60227-5
1. If the wire diameter is enlarged to 2×1
mm
2
, the total communication line length
can reach 1500 m.
2. The cord shall be Circular cord (the
cores shall be twisted together).
3. If unit is installed in places with intense
magnetic field or strong interference, it is
necessary to use shielded wire.
3.4 Wiring Requirements
Power Cord Size and Air Switch Capacity
Model
Power Cord Size
Air Switch
Capacity
(A)
Minimum Sectional
Area of Ground
Wire(mm
²
)
Minimum Sectional Area
of Power Cord
(mm
²
)
GMV-ND224PH/A-T
220-240V ~50Hz
208-230V ~60Hz
10
1.0
1.0
GMV-ND280PH/A-T
10
1.0
1.0
NOTES!
①
Use copper wire only as unit’s power cord. Operating temperature should be within its rated
value.
②
If the length of power cord is more than 15 m, please increase properly the sectional area of
power cord to avoid overload, which may cause accident.
③
Above selection requirements: Power cord size is based on BV single-core wire (2~4pc) at 40
℃
ambient temperature when laying across plastic pipe. Air switch is D type and used at 40
℃
. If
actual installation condition varies, please lower the capacity appropriately according to the
specifications of power cord and air switch provided by manufacturer.
④
Install cut-off device near the unit. The minimum distance between each stage of cut-off device
should be 3 mm (The same for both indoor unit and outdoor unit).