(8) The horizontal pipe can be connected to vertical pipe in the same level; please select the
connection way as shown in following Fig.
No.1: Connection of drainage pipe joints (Fig.4.3.6)
No.2: Connection of downspout elbow (Fig.4.3.7)
No.3: Inserting pipe connection (Fig.4.3.8)
Fig.4.3.6 Fig.4.3.7 Fig.4.3.8
(9) Drain pipes should have a downward slope of at least 1%~2%, in order to prevent pipes from
sagging, install hanger bracket at intervals of 1000~1500 mm.
Unit: mm
Fig.4.3.9
4.3.3 Test of Drainage System
(1) Inject some water to the water tray of indoor unit as following:
1) Connect the drain hose to the other drain connection pipe of water tray and inject
approximately 1L water. (Remove the drain hose after finishing testing and then put on the
plug of water tray.)
2) Spray 1L water on evaporator with sprayer.
Fig.4.3.10