Gree GMV-ND09TS/A-T Скачать руководство пользователя страница 9

Multi Variable Air Conditioners Two-way Cassette Indoor Unit

 

6

 

Wire type 

Total length of 

communication wire 

between indoor unit and 

indoor unit (outdoor unit) 

(m/ft.) 

Wire diameter 

(AWG) 

Wire standard 

Remark 

Light/Ordinary 

polyvinyl 

chloride 

sheathed 

cord. (60227 

IEC 52 

/60227 IEC 

53) 

L≤1000m 

(L≤3280-5/6ft.) 

≥2×0.75 

(≥2×AWG18) 

IEC 60227-5 

1. If the wire diameter is 

enlarged to 2×1 mm2 
(2×AWG16), the total 
communication line length 
can reach 1500 m (4921-
1/4ft.).   

2. The cord shall be Circular 

cord (the cores shall be 
twisted together). 

3. If unit is installed in places 

with intense magnetic field 
or strong interference, it is 
necessary to use shielded 
wire. 

3.4 Wiring Requirements 

Power Cord Size and Air Switch Capacity 

Model 

Power Supply 

MCA(A) 

MOP(A) 

GMV-ND09TS/A-T(U) 

208/230V-1ph-60Hz 

15 

GMV-ND12TS/A-T(U) 

15 

GMV-ND15TS/A-T(U) 

15 

GMV-ND18TS/A-T(U) 

15 

GMV-ND24TS/A-T(U) 

15 

 

(1) An all-pole disconnection switch having a contact separation of at least 3mm (1/8 in.) in all poles should 

be connected in fixed wiring. 

(2) The circuit breaker and power cord specification in above sheet is based on max power (max current) of 

the unit. 

(3) The power cord specification in above sheet is based on ambient temperature of 40(104°F). 

(4) The  circuit  breaker  specification  in  above  sheet  is  based  on  ambient  temperature  of  40(104°F).  If  the 

working condition is different, please adjust it according to the specification sheet of circuit breaker. 

 

 

 

Содержание GMV-ND09TS/A-T

Страница 1: ...anual Original Instructions Commercial Air Conditioners Multi Variable Air Conditioners Two way Cassette Indoor Unit Models GMV ND09TS A T U GMV ND12TS A T U GMV ND15TS A T U GMV ND18TS A T U GMV ND24...

Страница 2: ...ex factory date 2 Malfunction details before and after the malfunction occurs 7 Each unit has been strictly tested and proved to be qualified before ex factory In order to prevent units from being dam...

Страница 3: ...System Testing 10 4 4 Panel installation 13 4 5 Installation of Wired Controller 15 5 Wiring Work 15 5 1 Connection of Wire and Patch Board Terminal 15 5 2 Power Cord Connection 16 5 3 Connection of C...

Страница 4: ...sh water towards unit otherwise malfunction or electric shock may happen 17 Do not expose the unit to the moist or corrosive circumstances 18 Under cooling mode please don t set the room temperature t...

Страница 5: ...inage Pipe Connection Pipe Drainage Device Air Inlet Grille With Filter Main Unit Louver Panel 2 2 Rated Working Condition Indoor Side Condition Outdoor Side Condition Dry Bulb Temp C Wet Bulb Temp C...

Страница 6: ...e 5 Sponge 1 To insulate the drain pipe 6 Fastener 4 To fasten the sponge 7 paper pattern for installation 1 Locate the drill hole on ceiling 8 Tapping screw with washer 4 Fix paper pattern 9 Remote c...

Страница 7: ...d noise Even if the distance is 1m 39 3 8 in when there is strong electric wave noise may still occur Unit mm in Fig 3 2 1 1 The unit shall be installed in accordance with national standards or local...

Страница 8: ...t Ordinary polyvinyl chloride sheathed cord 60227 IEC 52 60227 IEC 53 L 250m L 820 1 5ft 2 0 75 2 1 25 2 AWG18 2 AWG16 IEC 60227 5 1 Total length of communication line can t exceed 250m 820 1 5ft 2 Th...

Страница 9: ...s necessary to use shielded wire 3 4 Wiring Requirements Power Cord Size and Air Switch Capacity Model Power Supply MCA A MOP A GMV ND09TS A T U 208 230V 1ph 60Hz 1 15 GMV ND12TS A T U 1 15 GMV ND15TS...

Страница 10: ...43 56 13 16 6 35 1 4 9 52 3 8 GMV ND12TS A T U GMV ND15TS A T U 1200 47 1 4 1252 49 5 16 1403 55 1 4 1443 56 13 16 6 35 1 4 12 7 1 2 GMV ND18TS A T U GMV ND24TS A T U 1200 47 1 4 1252 49 5 16 1403 55...

Страница 11: ...of the hanger bracket The washer fixing plate will prevent the washer from falling 3 The usage of paper pattern Refer to paper pattern of installation for ceiling opening dimension The center of ceili...

Страница 12: ...d then tighten the flaring nut with hand as shown in fig 4 2 1 2 Tighten the flaring nut with torque wrench Fig 4 2 1 3 Use pipe bend when bending the pipe and the bending angle should not be too smal...

Страница 13: ...the drainage pipelines are used for several units the position of pipeline should be about 100mm 4 in lower than the drainage port of each unit In this case thicker pipes should be applied Fig 4 3 1...

Страница 14: ...pe is vertical with the unit the raising height should be less than C Unit mm in Fig 4 3 3 Model A mm in B mm in C mm in GMV ND09TS A T U GMV ND12TS A T U GMV ND15TS A T U GMV ND18TS A T U GMV ND24TS...

Страница 15: ...e water over the electrical components e g water pump etc 2 In case of commissioning finished please energize the IDUs and switch to cooling or dry mode meanwhile the water pump operates you can check...

Страница 16: ...per decorative panel installation could cause the following problems Fig 4 4 1 2 Ensure that its clearance free between decoration panel and ceiling board after installation if not please adjust the b...

Страница 17: ...pipe Fig 4 4 4 2 Adjust the position of panel to make the panel holes fix at the holes on the unit 3 Fix the 4 screws at the two side of panel and then fix the 2 screws in the middle of panel 4 Insta...

Страница 18: ...ircuit breaker for branch circuit according to related regulations and electrical standards 6 Keep cable away from refrigerant pipings compressor and fan motor 7 The communication wires should be sepa...

Страница 19: ...ing operation all indoor units connected to the same outdoor unit system must be kept energized status Otherwise the unit can t operate normally Fig 5 2 1 For units with single phase power supply 1 De...

Страница 20: ...communication bus terminal D1 and D2 as shown in fig 5 3 2 terminal resistor is provided with each ODU 5 4 Connection of Communication Wire for Wired Controller 1 Detach the electric box cover 2 Let...

Страница 21: ...be set as master one and slave one 4 One wired controller can control 16 indoor unitS in maximum at the same time As shown in Fig 5 5 1 1 The type of indoor units must be the same if they are control...

Страница 22: ...Multi Variable Air Conditioners Two way Cassette Indoor Unit 19 Fig 5 5 1...

Страница 23: ...it If the filter is very dirty e g greasy you can clean it using warm water below 45 C that is mixed with mild detergent Then let it dry naturally in cool places 2 If the air conditioner is used in du...

Страница 24: ...Water Temperature Sensor Error L8 Power Insufficiency Protection d7 Humidity Sensor Error C0 Communication Error L9 Quantity Of Group Control Indoor Units Setting Error d8 Water Temperature Error AJ...

Страница 25: ...ked Too heavy heat load of room e g too many people Door or windows is open Inlet and outlet of IDU are blocked Setting temperature is too high or refrigerant leaks Refrigerant is insufficient e g ref...

Страница 26: ......