Multi Variable Air Conditioners Two-way Cassette Indoor Unit
11
Unit: mm (in.)
①
- drainage pipes assembled by T-shaped joints
Fig. 4.3.2
(8) The installation height of raising pipe for drainage should be lower than B. The
gradient from raising pipe towards drainage direction should be at least 1%
~
2%. If the raising pipe is vertical with the unit, the raising height sh ould be less
than C.
Unit: mm (in.)
Fig. 4.3.3
Model
A(mm(in.))
B(mm(in.))
C(mm(in.))
GMV-ND09TS/A-T(U)
GMV-ND12TS/A-T(U)
GMV-ND15TS/A-T(U)
GMV-ND18TS/A-T(U)
GMV-ND24TS/A-T(U)
260(11-3/4)
740(30-7/8)
690(27-3/16)
(9) Drainage pipes should have a downward slope of at least 1%
~
2%, in order to
prevent pipes from sagging; install hanger bracket at intervals of 1000
~
1500mm (39-3/8
~
59 in.).
Unit: mm (in.)
Fig. 4.3.4
(10) During the installation, distance from soft drain pipe to the gasket is C mm