Multi Variable Air Conditioners Ducted Type Indoor Unit
4
No.
Name
Appearance
Q'ty
Usage
6
M10 Washer (Spring Washer
M10X2.6)
4
To be used together with the hanger bolt for
installing the unit.
7
Insulation
1
To insulate the gas pipe
8
Insulation
1
To insulate the liquid pipe
9
Sponge
2
To insulate the drain pipe
10
Fastener
8
To fasten the sponge
3.2 Location for Installation
(1)
Th
is
appliance shall not be installed
a corrosive environment [i.e.
laundry
, etc.]
(2)
The framework the unit is attached to must be strong enough to support units
'
weight.
(3)
The condensate drain pipe must be properly sized/sloped to ensure proper drainage
.
(4)
Remove all
obstacle
s
at inlet or outlet
to e
nsure good air circulation.
(5)
Observe all dimensions below to ensure there's enough room for maintenance.
(6)
Keep the unit away from
any
heating source, inflammable gas or smoke.
(7)
This is a concealed ceiling type unit.
(8)
Indoor
and
outdoor unit
supply power
and
control
wir
ing
should
be
kept at least
1m(39-3/8
in.)
from
any
TV set
or
radio.
E
lectrical appliances may
create
interference
(
noise
)
e
ven
if
wiring is in excess of
1m(39-3/8 in.)
. S
trong
electric
al signals
may still
create
interference.
Unit: mm(in.)
Fig 3.2.1