64
Installation and Maintenance
Service Manual
9. Maintenance
9.1 Error Code List
No.
Malfunction
Name
Display Method of Indoor Unit
A/C status
Possible Causes
Dual-8
Code
Display
Indicator Display (during
blinking, ON 0.5s and OFF
0.5s)
Operation
Indicator
Cool
Indicator
Heating
Indicator
1
High
pressure
protection of
system
E1
During cooling and drying
operation, except indoor
fan operates, all loads stop
operation.
During heating operation, the
complete unit stops.
Possible reasons:
1. Refrigerant was superabundant;
2. Poor heat exchange (including
filth blockage of heat exchanger
and bad radiating environment );
Ambient temperature is too high.
2
Low pressure
protection of
system
E3
The Dual-8 Code Display will
show E3 until the low pressure
switch stop operation.
1.Low-pressure protection
2.Low-pressure protection of
system
3.Low-pressure protection of
compressor
3
High
discharge
temperature
protection of
compressor
E4
During cooling and drying
operation, compressor and
outdoor fan stop while indoor
fan operates. During heating
operation, all loads stop.
Please refer to the malfunction
analysis (discharge protection,
overload).
4
Overcurrent
protection
E5
During cooling and drying
operation, compressor and
outdoor fan stop while indoor
fan operates. During heating
operation, all loads stop.
1. Supply voltage is unstable;
2. Supply voltage is too low and
load is too high;
3. Evaporator is dirty.
5
Communi-
cation
Malfunction
E6
During cooling operation,
compressor stops while
indoor fan motor operates.
During heating operation, the
complete unit stops.
Refer to the corresponding
malfunction analysis.
6
High
temperature
resistant
protection
E8
During cooling operation:
compressor will stop while
indoor fan will operate.
During heating operation, the
complete unit stops.
Refer to the malfunction analysis
(overload, high temperature
resistant).
7
EEPROM
malfunction
EE
During cooling and drying
operation, compressor will stop
while indoor fan will operate;
During heating operation, the
complete unit will stop
Replace outdoor control panel AP1
8
Limit/
decrease
frequency
due to high
temperature
of module
EU
All loads operate normally,
while
operation frequency for
compressor is decreased
Discharging after the complete unit
is de-energized for 20mins, check
whether the thermal grease on
IPM Module of outdoor control
panel AP1 is sufficient and whether
the radiator is inserted tightly.
If its no use, please replace control
panel AP1.
9
Malfunction
protection of
jumper cap
C5
Wireless remote receiver and
button are effective, but can
not dispose the related
command
1. No jumper cap insert on
mainboard.
2. Incorrect insert of jumper cap.
3. Jumper cap damaged.
4. Abnormal detecting circuit of
mainboard.
Содержание CB385001000
Страница 1: ...Service Manual Change for life GREE ELECTRIC APPLIANCES INC OF ZHUHAI...
Страница 30: ...27 Technical Information Service Manual 873 376 330 5 555 GWH24AGD K6DNA1C O CB385W08603 Unit mm...
Страница 116: ...113 Installation and Maintenance Service Manual GWH18AGD K6DNA1A O...
Страница 117: ...114 Installation and Maintenance Service Manual...
Страница 118: ...115 Installation and Maintenance Service Manual...
Страница 119: ...116 Installation and Maintenance Service Manual Capillary Sub assy...
Страница 121: ...118 Installation and Maintenance Service Manual screws Rear Grill...
Страница 122: ...119 Installation and Maintenance Service Manual...
Страница 123: ...120 Installation and Maintenance Service Manual...
Страница 124: ...121 Installation and Maintenance Service Manual...
Страница 125: ...122 Installation and Maintenance Service Manual...