Once the spacer is placed over the male end of the device, twist the sections together until the parts are snug, and 
the carbon fiber brushes are pointing in the same direction, as shown in FIGURE 4A. Please note, once the bars are 
assembled, there should be no “wobble” between the sections. Proceed to 2.

Step 1B – Assembly of snap-type GPS-iMOD

Once the mounting location has been verified, assemble the modular sections by inserting the post-end of the iMOD 
into  the  receiver-end  of  the  first  modular  section  already  attached  to  the  powerhead  (see  FIGURE  7).  Attach  iMOD 
sections, making sure they are properly aligned as shown in FIGURE 8. Attach the iMOD sections by using a rubber 
mallet and carefully tapping with enough force to cause the modular sections to “snap” together (see FIGURE 9). Set 
iMOD on hard, flat surface when assembling with mallet. Hold iMOD firmly while tapping with hammer to avoid slipping.

Do not hold iMOD between sections while assembling to avoid pinching.

CAUTION: Once iMOD sections are snapped together, they cannot be disassembled without breaking off the end piece.

Continue assembling the modular sections until you reach the needed length for the coil. After assembling the 
first 8 iMOD sections, lay the assembly on floor with the powerhead firmly butted against a rigid wall. See FIGURE 
10. Continue to add iMOD sections until you reach the required length of the assembly. Proceed to 2.

2. Once the last iMOD section is added, push the nylon end cap into the receiver end of the last iMOD section. It 

will “snap” into place with proper pressure. Refer to FIGURE 11.

3. Verify all iMod sections are engaged and the end cap is installed prior to mounting in the air handler.

!

Содержание GPS-iMOD

Страница 1: ...www globalplasmasolutions com Installation Operation Maintenance Manual GPS iMOD NOTICE This product is to be used only as directed Read entire manual before use Do not use unless properly installed ...

Страница 2: ... mounting magnets per bar for securing the GPS iMOD to the cooling coil inlet on the downstream side of the filter rack Magnet quantity provided will increase based on overall bar length Refer to iMod Mounting section for recommended magnet spacing 6 Nylon screws and nuts for securing magnets to the front or back of the iMOD sections and metal screws for securing magnets to the top of the iMOD sec...

Страница 3: ...screw type GPS iMOD Once the mounting location has been verified assemble the modular sections by inserting the male threaded post into the female receiver of the first modular section already attached to the powerhead see FIGURE 3 and tighten until the modular housings are securely butted to each other See FIGURE 4 below for correct assembly alignment Please note it should take 3 4 complete revol...

Страница 4: ...cause the modular sections to snap together see FIGURE 9 Set iMOD on hard flat surface when assembling with mallet Hold iMOD firmly while tapping with hammer to avoid slipping Do not hold iMOD between sections while assembling to avoid pinching CAUTION Once iMOD sections are snapped together they cannot be disassembled without breaking off the end piece Continue assembling the modular sections unt...

Страница 5: ...13 with the carbon fiber brushes pointing towards the floor NOTE The clearance between the mounting surface and the side wall of the bar should be between 1 2 and 1 8 Failure to do may result in low ion density and poor performance Keep all metal away from carbon fiber brushes The ionization bar should always be mounted on the air entering side of the cooling coil Mounting the bar on the leaving s...

Страница 6: ...ER HIGH VOLTAGE CABLES Cables 15ft long can be ordered if additional length is required DO NOT coil bunch or loop the cable up so that it comes in contact with itself To reduce slack in the cable create long sweeping S shapes like switchbacks in a road High voltage cable should be routed with soft bends only such as creating long sweeping S shapes Minimum bend radius is 3 Secure the cable s so the...

Страница 7: ... must be connected to ground A grounded common will not suffice as adequate power supply grounding 1 The power supply may be mounted to the internal or external wall of the air handler 2 Find a location within reach of the high voltage cable extending from the GPS iMOD Remove the 4 screws securing the lid of the power supply 3 Mount the power supply to the wall using sheet metal screws through the...

Страница 8: ...n the GPS iDetect P terminal block see FIGURE 15 for jumper wire 2 Using 300V 18 4 plenum rated SHIELDED cable wire between the GPS iDetect P power and normally open terminals and the GPS iMOD power supply GPS iDetect P terminal block as shown in FIGURE 20 Ground the 18 4 SHIELD to the ground terminal on the GPS iDetect P terminal strip shown in FIGURE 20 Only ground ONE end of the shielded cable ...

Страница 9: ...d and wired energize the system by turning the on off switch to the on position The green power ON LED and PLASMA ON LED should illuminate If the PLASMA ON does not illuminate confirm the red jumper is installed between C and NO on the GPS iDetect P terminal block as shown in FIGURE 20 If the optional iDetect P is used confirm it is on and operating 3 Using a high voltage probe similar to a BK Pre...

Страница 10: ...em uses an internal auto reset circuit breaker Either a voltage surge or high temperature load condition can trip the circuit breaker If the Power On light is off and the Plasma On light is On the Power On light may have burned out Contact your local Representative or the GPS factory to have your power supply repaired or replaced 2 No Ionization Output Confirm the power supply is operating properl...

Страница 11: ...alplasmasolutions com 3101 Yorkmont Road Suite 400 Charlotte NC 28208 980 279 5622 2021 Global Plasma Solutions Inc To access a list of applicable patents please visit www gpspatents com GPS 041 11 R4 iMOD IOM ...

Отзывы: