background image

www.globalplasmasolutions.com

Operation

1. Once the voltage selector switch has been set, all HV wire(s) connected and iMODs mounted, turn the power 

switch to the “ON” position. When the switch is turned “ON” the “Power ON” light will illuminate, letting the 
user know power is supplied and the GPS-iMOD system is energized. Note: If a door switch, fan interlock 
switch or air flow switch are in series with the power, the system may not turn on until all safeties are closed. 
When power is supplied and the internal or optional remote mounted GPS-iDetect-P is sensing output, the 
“Plasma On” light will illuminate.

2. The internal BAS Alarm Contacts will close proving system operation to the BMS.
3. Using a standard non-contact voltage meter, place it near the ion needles and prove there is ion output. An 

optional ion meter can be purchased from GPS and actual ion output values can be measured. A permanent 
mount ion detector with BAS interface may be provided as an option for 24/7 output monitoring.

Startup/Testing

1. Prior to energizing the unit: verify voltage selector switch matches incoming voltage and that the power 

supply is properly grounded. 

2. Once the entire system is mounted and wired, energize the system by turning the on/off switch to the “on” 

position. The green power “ON” LED and “PLASMA ON” LED should illuminate. If the PLASMA ON does not 
illuminate, confirm the red jumper is installed between C and NO on the GPS-iDetect-P terminal block, as 
shown in FIGURE 20. If the optional iDetect-P is used, confirm it is on and operating.

3. Using a high voltage probe similar to a BK Precision Plus 28A, connect the probe to a multi-meter, connect 

the ground clamp, and measure the AC high voltage (AC not DC) at the 6 inch modular stingers. Insert the tip 
of the probe into one of the brush clusters and confirm the voltage is greater than 4,000 VAC. Please note, 
most probes provide a 1000:1 step down. As an example, a display of 4.0 would be 4.0 x 1000 = 4,000 VAC. 
The typical range of voltage is 4,000VAC to 7,000VAC, and the actual voltage will depend on the length and 
quantity of bars attached.

Maintenance

The GPS-iMOD system has been designed for minimum maintenance. Below are the steps to ensure a long trouble-free 
life:

1. On an annual basis, turn off power and use isopropyl alcohol and a nylon (wire free) brush to gently clean the 

needles.

2. Use a soft cloth with isopropyl alcohol and wipe any debris off the GPS-iMOD outer bar and spaces between 

needle housings.

3. Note: In high contaminant load environments, the GPS-iMOD will require more frequent cleaning.

Содержание GPS-iMOD

Страница 1: ...www globalplasmasolutions com Installation Operation Maintenance Manual GPS iMOD NOTICE This product is to be used only as directed Read entire manual before use Do not use unless properly installed ...

Страница 2: ... mounting magnets per bar for securing the GPS iMOD to the cooling coil inlet on the downstream side of the filter rack Magnet quantity provided will increase based on overall bar length Refer to iMod Mounting section for recommended magnet spacing 6 Nylon screws and nuts for securing magnets to the front or back of the iMOD sections and metal screws for securing magnets to the top of the iMOD sec...

Страница 3: ...screw type GPS iMOD Once the mounting location has been verified assemble the modular sections by inserting the male threaded post into the female receiver of the first modular section already attached to the powerhead see FIGURE 3 and tighten until the modular housings are securely butted to each other See FIGURE 4 below for correct assembly alignment Please note it should take 3 4 complete revol...

Страница 4: ...cause the modular sections to snap together see FIGURE 9 Set iMOD on hard flat surface when assembling with mallet Hold iMOD firmly while tapping with hammer to avoid slipping Do not hold iMOD between sections while assembling to avoid pinching CAUTION Once iMOD sections are snapped together they cannot be disassembled without breaking off the end piece Continue assembling the modular sections unt...

Страница 5: ...13 with the carbon fiber brushes pointing towards the floor NOTE The clearance between the mounting surface and the side wall of the bar should be between 1 2 and 1 8 Failure to do may result in low ion density and poor performance Keep all metal away from carbon fiber brushes The ionization bar should always be mounted on the air entering side of the cooling coil Mounting the bar on the leaving s...

Страница 6: ...ER HIGH VOLTAGE CABLES Cables 15ft long can be ordered if additional length is required DO NOT coil bunch or loop the cable up so that it comes in contact with itself To reduce slack in the cable create long sweeping S shapes like switchbacks in a road High voltage cable should be routed with soft bends only such as creating long sweeping S shapes Minimum bend radius is 3 Secure the cable s so the...

Страница 7: ... must be connected to ground A grounded common will not suffice as adequate power supply grounding 1 The power supply may be mounted to the internal or external wall of the air handler 2 Find a location within reach of the high voltage cable extending from the GPS iMOD Remove the 4 screws securing the lid of the power supply 3 Mount the power supply to the wall using sheet metal screws through the...

Страница 8: ...n the GPS iDetect P terminal block see FIGURE 15 for jumper wire 2 Using 300V 18 4 plenum rated SHIELDED cable wire between the GPS iDetect P power and normally open terminals and the GPS iMOD power supply GPS iDetect P terminal block as shown in FIGURE 20 Ground the 18 4 SHIELD to the ground terminal on the GPS iDetect P terminal strip shown in FIGURE 20 Only ground ONE end of the shielded cable ...

Страница 9: ...d and wired energize the system by turning the on off switch to the on position The green power ON LED and PLASMA ON LED should illuminate If the PLASMA ON does not illuminate confirm the red jumper is installed between C and NO on the GPS iDetect P terminal block as shown in FIGURE 20 If the optional iDetect P is used confirm it is on and operating 3 Using a high voltage probe similar to a BK Pre...

Страница 10: ...em uses an internal auto reset circuit breaker Either a voltage surge or high temperature load condition can trip the circuit breaker If the Power On light is off and the Plasma On light is On the Power On light may have burned out Contact your local Representative or the GPS factory to have your power supply repaired or replaced 2 No Ionization Output Confirm the power supply is operating properl...

Страница 11: ...alplasmasolutions com 3101 Yorkmont Road Suite 400 Charlotte NC 28208 980 279 5622 2021 Global Plasma Solutions Inc To access a list of applicable patents please visit www gpspatents com GPS 041 11 R4 iMOD IOM ...

Отзывы: