![GPS GPS-iMOD Скачать руководство пользователя страница 5](http://html.mh-extra.com/html/gps/gps-imod/gps-imod_installation-operation-and-maintenance-manual_2248998005.webp)
www.globalplasmasolutions.com
iMOD Mounting
The included magnets can be used as a spacer even when installing on non-magnetic surfaces. Care should be taken
when selecting self tapping screws to avoid penetrating the cooling coil.
4. The GPS-iMOD modular sections can be mounted using the included magnets and hardware, or they can be
mounted using sheet metal screws (not provided) through the integral molded brackets. There should be
at least one magnet mounted on each end of the bar assembly and depending on length of bar, magnets
should be mounted on every third section (roughly 18” spacing between magnets). Refer to FIGURE 12
for examples of top or side magnet mount installations. Nylon screws and nuts are provided by GPS for
mounting the magnets to the front or back of the bar.
5. When mounting the GPS-iMOD, the bottom of the GPS-iMOD should be level with top of the finned surface
area of the coil as shown in FIGURE 13, with the carbon fiber brushes pointing towards the floor.
NOTE:
The clearance between the mounting surface and the side wall of the bar should be between 1/2” and 1/8”.
Failure to do may result in low ion density and poor performance.
Keep all metal away from carbon fiber brushes. The ionization bar should always be mounted on the air-
entering side of the cooling coil. Mounting the bar on the leaving side of the coil (drain pan and wet side) will
not keep the coil clean. The GPS-iMOD (SCREW TYPE ONLY) powerhead may be rotated to provide the best
power cord routing based on the installation. Refer to FIGURE 14. When more than one bar is required per
coil, mount the second bar half-way down the coil with the needles pointing towards the floor.
Do not cut or alter high voltage cable. Use grommets for any holes or protrusions. High voltage wires should be
routed so no bend is less than a 3” bend radius (6” diameter for 180° high voltage cable routing).
NOTE:
The installing contractor will need to provide a piece of metal angle across the face of the coil to attach the
GPS-iMOD if the coil finned surface area is over 3 feet wide.