IF VOLTAGE OTHER THAN 24VAC IS BEING SUPPLIED, USE APV-12-24 POWER SUPPLY INCLUDED WITH 

FC-3T

240VAC installation

1. Find a suitable location for the APV-12-24. Secure the APV-12-24 with self-tapping screws

or double-sided tape.

2. Route the wires so that they will not short, abrade, or damage other components
3. Connect the FC-3 to the low voltage side of APV-12-24 (red and black wires) red to red and black to black.

a. Twist-on wire connectors (Figure 7) and crimp connectors (Figure 6) are both acceptable methods

of connecting low voltage wires.

4. Connect the high voltage side of APV-12-24 (blue and brown wires) to the terminal block where the 240v

wires enter HVAC unit.

5. Connect the orange wires to the Building Automation System wires or terminals (if present). If no BAS system

is present, then insulate ends of wires and secure wires where they will not be damaged.

120 VAC installation

1. Find a suitable location for the APV-12-24. Secure the APV-12-24 with self-tapping screws or double-sided

tape.

2. Route the wires so that they will not short, abrade, or damage other components
3. Connect the FC-3 to the low voltage side of APV-12-24 (red and black wires) red to red and black to black.
a. Twist-on wire connectors (Figure 7) and crimp connectors (Figure 6) are both acceptable methods of connect-

ing low voltage wires. .

4. Connect the neutral leg of power to the blue wire. Connect the line or power leg to the brown wire
5. Connect the orange wires to the Building Automation System wires or terminals (if present). If no BAS system

is present, then insulate ends of wires and secure wires where they will not be damaged.

Figure 5: 120V/240V Input Power Wiring Diagram

!

Содержание GPS-FC-3

Страница 1: ...Installation Operation Maintenance Manual GPS FC 3 3T BAS NOTICE This product is to be used only as directed Read entire manual before use Do not use unless properly installed ...

Страница 2: ...s with the FC 3 Hardware Provided by GPS FC 3 unit Fuse Additional Hardware Provided by GPS with FC 3T model Power supply APV 12 24 required for installations on voltages higher than 24VAC Hardware Required by Installer Mounting screws Electrical connectors Twist on wire connectors or comp connectors Double sided tape INSTALLATION LOCATION GPS recommends the FC 3 be installed downstream from the f...

Страница 3: ... will not damage refrigerant lines wires or other components When attaching the FC 3 to a grille or screen nylon ties may be used 3 The FC 3 ion emitters should not be touching any metal surface or wires Move and secure any wires that may come in contact with the ion emitters CAUTION THE NEEDLES MUST BE 2 INCHES AWAY FROM METAL SURFACES TO PREVENT ARCING NOTE Use Temperature Maximum Ambient temper...

Страница 4: ...ystem wires or terminals if present If no BAS system is present then insulate ends of wires and secure wires where they will not be damaged 120 VAC installation 1 Find a suitable location for the APV 12 24 Secure the APV 12 24 with self tapping screws or double sided tape 2 Route the wires so that they will not short abrade or damage other components 3 Connect the FC 3 to the low voltage side of A...

Страница 5: ...uld indicate voltage Maintenance CAUTION MAKE SURE POWER IS DICONNECTED BEFORE SERVICING The FC 3 requires very little maintenance Over time particles will accumulate on the ion emitters and they will need to be cleaned periodically In most applications annual cleaning will suffice 1 Turn power to the FC 3 off 2 Gently brush the ion emitters with a nylon brush toothbrush will work 3 Restore power ...

Страница 6: ...21 Global Plasma Solutions Inc To access a list of applicable patents please visit www gpspatents com GPS 041 16 R5 FC3 3T IOM ZERO OZONE EMISSIONS MEASURED OZONE EMISSIONS FROM GPS FC 3 BAS DURING USE PHASE DOES NOT EXCEED 0 005 PPM AS TESTED BY UL 867 UL COM ECV ...

Отзывы: