 To power some low power pickup/display devices, such as a GPI 

“EDM” module, a loop powered GX500 can supply 5 VDC at up to ap-

proximately 2.5 mA without degrading conversion accuracy. However, “ac-

tive” pickup devices or conditioners (i.e., Hall Effect or R-F) usually require 

more current. If such a device is used, or if you use the optically isolated 

inputs, you must provide an independent, isolated DC power supply to 
operate the pickup circuitry.

**

 

 If you want to use the 4-20 mA output 

and

 one or both of the other 

outputs at the same time, you must provide electrical isolation between 

the current loop and all other circuit elements. Failure to do so will result in 

incorrect 4-20 mA signal conversion, and possible damage to the unit.

SPECIFICATIONS  –  REMOTE  MODEL

Applications:

Use for indoor or outdoor applications where occasional 

moisture is common.

Materials:

Acetal,  Amorphous  Nylon,  Silicone  Rubber,  Polyester 

(decals), Viton (gasket & seals), Stainless Steel (fasteners), 

PVC (cable jacket)

Power Source:

2-wire, loop powered

*

. 8.5 VDC to 35 VDC loop voltage 

required for correct operation.

Outputs

**

:

Analog Primary:  4-20 mA current loop. (This is also the 

power  supply  input  for  the  module.)  With  loop  voltage 

maintained within specified limits, will maintain advertised 

linearity over 4 mA to 20 mA range, with good linearity 

in  over-range  conditions  to  about  1.5  mA  and  25  mA. 

Absolute  maximum  current  limit  under  fault  conditions 

approximately 35 mA.
Analog Auxiliary:  0 to 5 VDC. Relationship to primary cur-

rent output: V(volts) = l (ma) ÷ 5 . Will maintain advertised 

linearity over 0.8 V to 4.0 V range, with good linearity in 

over-range conditions to about 0.1 V and 4.9 V.

Recommended minimum driven impedance = 10K Ohms.
Digital  (Pulse  Out):    Open  Collector,  square  wave.  Will 

switch up to 60 V and up to 200 mA. Closed circuit voltage 

drop typically 0.1 V; guaranteed less than 0.5 V at any in 

range current.

Configuration:

2-Totals (1 cumulative and 1 batch), Rate, 2 Cals

(Factory calibration in gallons or litres; 1 field calibration),

K-factor to match published K-factor for each size meter.

Time Base:

Hours or minutes

Unit of Measure:

U.S. gallons or litres

Frequency Limits for Correct Operation:

 

 

Display and

Input Type  Analog Conversion 

Digital Output

LLC (sine):  approx. 11-1000 Hz  approx. 0-1000 Hz

HLLF: 

0.25-150 Hz 

0-150 Hz

HLHF: 

0.25-1200 Hz 

0-1200 Hz

Optically Isolated HLLF:  same as standard HLLF

Optically Isolated HLHF:  same as standard HLHF

Accuracy/Performance:

Max. Conversion Error:  (nonlinearity plus span, any input, 

loop current output, 0°C to 70°C, loop voltage supply 12 

VDC to 24 VDC) 0.5% of span plus possible resolution 

uncertainty. Coupled flowmeter may add additional error.
Max. Conversion Resolution Uncertainty:  (Loop current 

output, when properly calibrated) Larger of 0.1 mA or 

[20 mA / (10 x ( f

20

–f

4

)]. Where f

20

 = frequency at 20 mA, 

f

= frequency at 4 mA.

Speed of Response:  After step change in input frequency, 

loop output guaranteed stable within 3 x accumulating time 

(Accumulating time user selectable from 0.3 sec, 0.7 sec, 

1.3 sec, 2.6 sec, 5.2 sec).

Batch Total:

Up to 999,999 (x100)

Cumulative Total:

Up to 999,999 (x100)

Ambient Temperature:

+32° F to +140° F  (0° C to +60° C)

Cable:

20 feet, 3-conductor (red, black & white), tinned drain wire, 

22 AWG, PVC jacket .212 dia., (Reference Belden 9363 or 

equivalent cable)

Mechanical Connections:

Wall  or pipe mountable with standard U-bolts

Electrical Connections:

GX500 - Two strain relief ports

GX510 - One strain relief port: one threaded plug

G2 Series - Two strain relief ports

GM Local Models - Two strain relief ports

GM 1/2 in. and Larger - One strain relief port: one 

threaded plug

Shipping Weight:

1.1 lb. (.5 kg)

Содержание GM001

Страница 1: ...CONTENTS To the owner Congratulations on receiving your GPI 4 20 mA Out with Display We are pleased to provide you with a product designed to give you maximum reliability and efficiency Our business i...

Страница 2: ...in indoor or outdoor applications where occasional exposure to moisture is common The 4 20 mA Out with Display is available in two ver sions One indicates flowrate in units minute and one in units ho...

Страница 3: ...her liquids occasional low pressure splashing will not harm unit if cable entry points are well sealed subject to 5g shock loading facing the sun directly for long periods of time close to high voltag...

Страница 4: ...m ONLY Local Com HL HF IN R See note EDM Power INPUTS OUTPUTS 4 20 mA Out with Display Loop Loop current current Min V 8 5 Max V 35 Customer Equipment Minimum signal amplitude required for normal oper...

Страница 5: ...Max V 35 Customer Equipment Loop Power Supply Typ 12 24 VDC Loop Input Loop Input NOTE 1 Loop power supply electrically isolated from customer equipment NOTE 2 Actual value of loop current mA is disre...

Страница 6: ...Frequency Generating Input Device INPUTS OUTPUTS 4 20 mA Out with Display Loop Loop current current Customer Equipment Loop Power Supply Typ 12 24 VDC Open Collector Pulse In Pulse In Return Pulse Ou...

Страница 7: ...that the enclosure sealisnotcrimpedortwisted Donotover tightencornerscrews hand tighten only Faceplate can be rotated 90 W I R I N G D I A G R A M 8 4 20 mA or 0 20 mA Output Customer Equipment Witho...

Страница 8: ...4 20 mA and Pulse Output option available only with Reed Switch input W I R I N G D I A G R A M 1 0 4 20 mA or 0 20 mA Output and Pulse Output Customer Equipment With Built in Power Supply Input Reed...

Страница 9: ...button for 3 seconds to reset the Batch Total to zero When fluid is flowing through the meter a small propeller icon is highlighted Flowrate Feature Tousethisfeature pressandreleaseDISPLAYuntilFLOWRA...

Страница 10: ...ser to tweak the factory calibration by a percent that represents application fluid or plumbing differences 1 To calibrate press and hold the CALIBRATE and DISPLAY buttonsforabout3secondsuntilyouseeFL...

Страница 11: ...the transmitter If signal is being received deactivate it by one of the following methods Stop the flow through the line that is being recorded Disconnect the output device on the flowmeter Locking U...

Страница 12: ...presently operating temporarily disable its external power supply Be sure to allow at least 30 seconds to elapse with unit unpowered 2 Press and hold the 4 button While holding watch the indicator li...

Страница 13: ...signal input connections for intermittent open or short circuits F LOOP OUTPUT 1 Output response time setting too long Select a shorter response time setting STABLE BUT especially for fast input sign...

Страница 14: ...14 DIMENSION DRAWINGS...

Страница 15: ...Tapping GM001 GM002 and GM003 2 9 120058 01 Bracket 1 10 904005 13 Screw 6 32 x 1 2 in 4 Item No No Part No Description Req d 11 904002 44 Screw 8 32 x 5 16 in 2 12 125066 20 Cable 20 ft 1 125066 3 C...

Страница 16: ...linearity plus span any input loop current output 0 C to 70 C loop voltage supply 12 VDC to 24 VDC 0 5 of span plus possible resolution uncertainty Max Conversion Resolution Uncertainty Loop current o...

Страница 17: ...gital Pulse Out Open Collector square wave Will switch up to 60 V and up to 200 mA Closed circuit voltage drop typically 0 1 V guaranteed less than 0 5 V at any in range current Configuration 2 Totals...

Страница 18: ...Please contact GPI before returning any part It may be possible to diagnose the trouble and find a solution with a telephone call GPI can also inform you of any special require ments you will need to...

Страница 19: ......

Страница 20: ...rranty shall not apply if A the product has been altered or modified outside the warrantor s duly appointed representative B the product has been subjected to neglect misuse abuse or damage or has bee...

Отзывы: