GPI GM001 Скачать руководство пользователя страница 12

12

Changing Response Time

The  4-20  mA  with  Display  comes  from  the  factory  with  a 

default 0.7 seconds response time.

 

If you reset the response time (procedure detailed be-

low) you MUST then reset the 4-20 mA endpoints.

To  give  good  performance  with  a  variety  of  sensor  types, 

many  frequency-to-analog  converters,  including  the  GPI 

4-20  mA  Out  with  Display,  offer  two  or  more  settings  for 

“response time” (sometimes referred to as “settling time” or 

“averaging time”).

 

  •  Longer (slower) response times are needed for sensor 

types  that  generate  very  low  frequency  outputs  (like 

GM Series oval gear flowmeters).

 

  •  Operating  a  meter  at  high  flowrates  may  require  a 

shorter  (faster)  response  time  to  achieve  the  best 

transmitter performance.

 

  •  Shorter (faster) response times are preferable for sen-

sors that generate higher frequency outputs (GPI turbine 

meters, for example). 

 

  •  Longer (slower) response times are also appropriate in 

situations where sensor-output frequency fluctuates or 

wobbles substantially.

 

The GPI 4-20 mA Out with Display offers a choice of five re-

sponse-time settings, selectable by the unit’s pushbuttons.

Procedure

1.  Start  with  the  unit  unpowered.  If  the  unit  is  presently 

operating, temporarily disable its external power supply. 

Be sure to allow at least 30 seconds to elapse with unit 

unpowered.

 

2.  Press  and  hold  the  “4”  button.  While  holding,  watch 

the indicator light and power up the 4-20 mA Out with 

Display.

3.  Shortly after power is applied, the light will blink one or 

more times. Count the number of blinks (from 1 to 5 blinks) 

and release the button after the blinking has finished.

 

NOTE:    If  necessary,  repeat  steps  1  through  3  to  get  the 

number  of  blinks  corresponding  to  the  response  time 

you want.

 

 

Blinks    

Response Time

 

1 blink   

0.3 second

 

2 blinks   

0.7 second

 

3 blinks   

1.3 second

 

4 blinks   

2.6 second

 

5 blinks   

5.2 second

 

In normal operation, the 4-20 mA Out with Display always av-

erages two sequential input readings. The time delay from an 

abrupt change in input frequency to a final, stabilized output 

reading is always twice that shown in the above table.

MAINTENANCE

Check cable-entry seals periodically. Tighten and/or apply 

sealant  if  needed.  This  is  especially  important  in  environ-

ments containing heavy concentrations of dust, oil mist, or 

other residue.
Check  all  wiring  connections  occasionally  for  oxidation  or 

corrosion. Clean and re-seat if such conditions are noted.
If necessary, check and re-seat any connections that may 

have been subjected to strain (during rework or construction, 

for example).

WARNING

Содержание GM001

Страница 1: ...CONTENTS To the owner Congratulations on receiving your GPI 4 20 mA Out with Display We are pleased to provide you with a product designed to give you maximum reliability and efficiency Our business i...

Страница 2: ...in indoor or outdoor applications where occasional exposure to moisture is common The 4 20 mA Out with Display is available in two ver sions One indicates flowrate in units minute and one in units ho...

Страница 3: ...her liquids occasional low pressure splashing will not harm unit if cable entry points are well sealed subject to 5g shock loading facing the sun directly for long periods of time close to high voltag...

Страница 4: ...m ONLY Local Com HL HF IN R See note EDM Power INPUTS OUTPUTS 4 20 mA Out with Display Loop Loop current current Min V 8 5 Max V 35 Customer Equipment Minimum signal amplitude required for normal oper...

Страница 5: ...Max V 35 Customer Equipment Loop Power Supply Typ 12 24 VDC Loop Input Loop Input NOTE 1 Loop power supply electrically isolated from customer equipment NOTE 2 Actual value of loop current mA is disre...

Страница 6: ...Frequency Generating Input Device INPUTS OUTPUTS 4 20 mA Out with Display Loop Loop current current Customer Equipment Loop Power Supply Typ 12 24 VDC Open Collector Pulse In Pulse In Return Pulse Ou...

Страница 7: ...that the enclosure sealisnotcrimpedortwisted Donotover tightencornerscrews hand tighten only Faceplate can be rotated 90 W I R I N G D I A G R A M 8 4 20 mA or 0 20 mA Output Customer Equipment Witho...

Страница 8: ...4 20 mA and Pulse Output option available only with Reed Switch input W I R I N G D I A G R A M 1 0 4 20 mA or 0 20 mA Output and Pulse Output Customer Equipment With Built in Power Supply Input Reed...

Страница 9: ...button for 3 seconds to reset the Batch Total to zero When fluid is flowing through the meter a small propeller icon is highlighted Flowrate Feature Tousethisfeature pressandreleaseDISPLAYuntilFLOWRA...

Страница 10: ...ser to tweak the factory calibration by a percent that represents application fluid or plumbing differences 1 To calibrate press and hold the CALIBRATE and DISPLAY buttonsforabout3secondsuntilyouseeFL...

Страница 11: ...the transmitter If signal is being received deactivate it by one of the following methods Stop the flow through the line that is being recorded Disconnect the output device on the flowmeter Locking U...

Страница 12: ...presently operating temporarily disable its external power supply Be sure to allow at least 30 seconds to elapse with unit unpowered 2 Press and hold the 4 button While holding watch the indicator li...

Страница 13: ...signal input connections for intermittent open or short circuits F LOOP OUTPUT 1 Output response time setting too long Select a shorter response time setting STABLE BUT especially for fast input sign...

Страница 14: ...14 DIMENSION DRAWINGS...

Страница 15: ...Tapping GM001 GM002 and GM003 2 9 120058 01 Bracket 1 10 904005 13 Screw 6 32 x 1 2 in 4 Item No No Part No Description Req d 11 904002 44 Screw 8 32 x 5 16 in 2 12 125066 20 Cable 20 ft 1 125066 3 C...

Страница 16: ...linearity plus span any input loop current output 0 C to 70 C loop voltage supply 12 VDC to 24 VDC 0 5 of span plus possible resolution uncertainty Max Conversion Resolution Uncertainty Loop current o...

Страница 17: ...gital Pulse Out Open Collector square wave Will switch up to 60 V and up to 200 mA Closed circuit voltage drop typically 0 1 V guaranteed less than 0 5 V at any in range current Configuration 2 Totals...

Страница 18: ...Please contact GPI before returning any part It may be possible to diagnose the trouble and find a solution with a telephone call GPI can also inform you of any special require ments you will need to...

Страница 19: ......

Страница 20: ...rranty shall not apply if A the product has been altered or modified outside the warrantor s duly appointed representative B the product has been subjected to neglect misuse abuse or damage or has bee...

Отзывы: