Device Description
English, Revision 03, Date: 11.05.2017
15
2.5.5.4.6
Software Version
2.5.5.4.7
Save Parameter
By writing the signature „save“ in ASCII code (hex-Code: 0x65766173) or „evas“ (hex-
Code: 0x73617665) on subindex 1 the current parameters are permanently stored. A
successful saving process will be confirmed after 2 ms by the TxSDO (1st Byte =
0x60).
2.5.5.4.8
Restore Default Parameter
By writing the signature „load" in ASCII- Code (hex-Code: 0x64616F6C) or „daol" (hex-
Code:0x6CdF6164 on sub index1 the corresponding default parameters are loaded.
A reset is recommended. Additionally „Restore All“ sets the baud rate to 125 Kbaud.
2.5.5.4.9
Producer Heartbeat Time
If 0 is entered for the time, this feature is disabled.
Index
Subindex
Name
Type
Attr.
Map
Default
Meaning
0x100A
00
Software
Version
Vis.-String
RO
NO
„1.00“
„Version of the
controller firm-
ware“
Table 17
CAN: Software Version
Index
Sub Index
Name
Type
Attr.
Map
Default
Meaning
0x1010
00
Save
Parameter
unsigned 8
RO
No
0x01
Number of sub
indexes
01
Save All
unsigned 32
RW
No
0x00000001
Save all is possi-
ble
Table 18
CAN: Save Parameter
Index
Sub Index
Name
Type
Attr.
Map
Default
Meaning
0x1011
00
Restore
Parameter
unsigned 8
RO
No
0x01
Number of sub
indexes
01
Restore All
unsigned 32
RW
No
0x00000001
Restore all is pos-
sible
Table 19
CAN: Restore Default Parameter
Index
Sub Index
Name
Type
Attr.
Map
Default
Meaning
0x1017
00
Producer
Heartbeat
Time
unsigned 16
RW
No
1000
Heartbeat time in
ms (approx.)
0, 10 ... 65535
Table 20
CAN: Producer Heartbeat Time