GOSSEN-METRAWATT GMBH
8
Physical installation / Getting started
Bild 2, Case dimensions and panel cutout
The R2600 / R2601 is meant for panel installation. As far as possible, the mounting
site should be free from vibrations. Aggressive vapors reduce the service life of the
controller. Observe the VDE 0100 specifications when performing any work. Work on
the controller must only be performed by a qualified person who is familiar with the
danger involved.
From the front, insert the case into the cutout and from the rear, fasten it at the top
and bottom with the two screw clamps supplied. The typical starting torque is
10 Ncm and should not exceed 20 Ncm.
Side-by-side mounting of several units is possible without intermediate bars. The
supplied seals for maintaining protection class IP54 cannot be used in this case.
Protection class IP54 is only assured in the case of a sunk rotary button.
When installing one or more units, it is a general requirement to provide for unob-
structed air circulation. The ambient temperature below the units must nor exceed
50 °C.
Withdrawing the instrument module (e.g. for setting of the DIP switch):
– Hold the instrument module on the front at tray and diaphragm between thumb and
forefinger (the pressure exerted on the diaphragm unlocks the plug-in module)
– Pull strongly
48
96
90
109
12
45
+0.6
92
+0.8
45
+0.6
92
+0.8
R2600
R2601