GOSSEN-METRAWATT GMBH
33
Evaluation of the trial run
– Apply a tangent to the curve at intersection P of actual value and set point and/or switch-off point of the output.
– Measure out time
∆
t
.
– Measure out oscillation width
x
ss
, for step controller overshoot
∆
x
.
If a limitation was set for the set point, it is required to correct the proportional band
Y H
positive: Multiply
Pb I
by 100 %
/
Y H
Y H
negative: Multiply
Pb II
by –100 %
/
Y H
Parameter values
tu
1.5
•
∆
t
∆
t – (
tY
/ 4)
tc
tu
/ 12
tY
/ 100
Pb I
(x
ss
/ MBU)
•
100 %
(x
ss
/ MBU)
•
200 %
(
∆
x / MBU)
•
50 %
Pb II
–
Pb I
•
(T
I
/ T
II
)
–
Pb I
•
(T
I
/ T
II
)
–
Parameter
Two-state controller
3-state controller
Contin. controller
Split range controller
Step controller
P
∆
t
∆
x
x
ss
T
I
T
II
dbnd
=
0
dbnd
=
MBU
(only for three-state/split range controller)