Technical data
See Data Sheet, Ordering No. 3-348-797-03 for complete technical data
Climatic suitability with reference to VDI/VDE 3540
3z / 0 / 50
Relative humidity, annual average, no condensation
75 %
Ambient temperature
Nominal range of use
Function range
Storage range
0
°
C ... + 50
°
C
0
°
C ... + 50
°
C
–25
°
C ... + 70
°
C
Aux. voltage
Nominal range of use
Power consumption
Nominal value
Voltage
Frequency
AC 110 V
AC 230 V
AC 24 V
AC 95 V ... 121 V
AC 196 V ... 253 V
AC 21 V
... 26 V
48 Hz ... 62 Hz
Maximum 10 VA
Typically 6 W
DC 24 V
DC 20 V
... 30 V
–
Relay output
Potential-free NOC (switcher)
Switching power
AC/DC 250 V, 2 A, 500 VA / 50 W
Service life
> 2
•
10
5
switching cycles under nominal load
Interference suppression
Provide ext. RC element (100
Ω
- 47 nF)
on contactor
Transistorized output suited for commercially available solid state relays (SSR)
Switching state
No-load voltage
Output current
Active (load
≤
800
Ω
)
< DC 17 V
10 ... 15 mA
Inactive
< DC 17 V
< 0.02 mA
Overload limit
Short circuit, cont. interruption
Electrical safety
Protection class
II, mounting equipment in the sense of DIN EN 61010-1
clause 6.5.4
Pollution degree
1, acc. to DIN EN 61010-1 clause 3.7.3.1 and/or IEC 664
Overvoltage category
II, acc. to DIN EN 61010 appendix J and/or IEC 664
Working voltage
300 V acc. to DIN EN 61010
EMC generic emission
DIN EN 50081-2
EMC generic immunity
DIN EN 50082-2