Setting parameters
X1 = lower range limit, X2 = upper range limit, MBU (range span) = X2 – X1
Parameter
Display
Range
Default
Remarks
High limit for relay A1
oFF, 1 ... MBU
oFF, X1 ... X2
oFF
oFF
Relative (= standard config.)
Absolute
Parameter disabled
at DIP switch
position shown
Low limit for relay A1
High limit for relay A2
Low limit for relay A2
Second set point
SP L
...
SP H
X1
Ramp for rising set points
oFF, 1 ... MBU per min
oFF
Ramp for falling set points
oFF, 1 ... MBU per min
oFF
Set point of the heat. curr.
(see calibr.)
Auto, oFF, 0.1 ...
A H
oFF
Not for step controller
1)
Proportional band Heat
0.1 ... 999.9 %
10.0
Parameter disabled
at DIP switch
position shown
and during
self-optimizing
Proportional band Cool
0.1 ... 999.9 %
10.0
For three-state controller
2)
Deadband
0 ... MBU
0
Not for 2-state controller
3)
Delay time of the controlled system
0 ... 9999 s
100
Cycle output time
0.5 ... 600.0 s
10.0
4)
Motor running time
5 ... 5000 s
60
For step controller only
5)
Switching hysteresis
0 ... 1.5 %MBU
0,5 %
MBU
for limit value monitoring
and limit monitor
1 2 3 4 5
1 2 3 4 5