Heating circuit monitor
Function
– Active / inactive configurable with the configuration digit "Alarms" (see Configuration)
–Without external transformer, without additional parameters
–Correct optimization of the control parameters
tu
and
Pb I
is a pre-condition!
i.e. before self-optimization is started, heating circuit monitoring must be activated.
The lower limit for the
tu
parameter must be maintained for manual optimization or subsequent adjustment of the control
parameters:
Pb I
MBU
minimum
tu =
•
50%
∆ϑ
⁄
∆
t
∆ϑ
⁄
∆
t = maximum temperature rise during start-up
–The error message
LE
is generated after approximately 2 times
tu
if the heater remains switched on 100 % and
the increase in temperature is too small
–The monitor is inactive, when
Controller type = limit monitor, positioner or step controller
During self-optimizing
With standard signal input (marking B2)
The limitation of the regulation ratio
Y H
< 20 %