installer or dealer. To replace filters, perform the following 
functions: 
1.  Turn Air Cleaner power switch 

OFF

2.  Turn off system fan. 
3. Open 

access 

door. 

4.  Remove collecting cells from Air Cleaner. 
5.  Remove the used carbon filters from Air Cleaner.  
6.  Put new carbon filters into Air Cleaner. Space filters 

evenly across the discharge opening of Air Cleaner. 
Never put more than 3 carbon filters in the Air 
Cleaner, as this may cause a problem with airflow. 

SERVICE

 

The Air Cleaner when operating normally, with the 

fan running, should have both the switch light and the 
performance indicator light 

ON

. If the fan is running and 

the lights are not on see the Troubleshooting Guide for 
probable causes and remedies. 

 

Quick Check 

(Power Light ON, Performance

 

Light OFF)

 

1.  Make sure the 

system fan is ON

Remove both 

cells

2.  Close the door. If the light is still out, check the 

power board for an arc to ground at HV1 or HV2. If 
there is a good arc and no performance light then 
replace the light. If the light comes on check the 
cells for a fault. 

3.  If there is no arc, test the output voltage of the 

transformer. If there is transformer output replace 
the power board 

4.  If there is no transformer output, check for output of 

the APS. 

5.  If there is output from the APS, replace the 

transformer and retest the power board for an arc. 

6.  If there is no output from the APS, jumper terminals 

3 & 4 on the APS and retest the output. If there is 

APS output with the jumper, replace the APS. 

7.  If there is no output from the APS, check the output 

voltage from the on/off switch. 

8.  If there is no voltage from the switch, test the input 

to the switch. If there is input, replace the switch. If 
there is no input to the switch, check the interlock 
switch and the supply voltage. 

 

Testing For High Voltage At Power Board 

With the 

collecting cells out of the unit

, the door on 

the unit and the system fan on high speed, turn the Air 
Cleaner 

ON

.  

With a long shafted screwdriver, with a plastic 

handle, short between the grounded side of the power 
box and the HV1 terminal of the power board. 

If you draw a good spark, there is high voltage from 

the power board.  

 

Measuring High Voltage At Power Board

 

A high voltage meter capable of measuring up to 

10,000 VDC is required to test the voltage. 
1.  The Air Cleaner should be 

ON

 with the cells installed, 

the door closed and the system fan running. The Air 
Cleaner should be on at least 5 minutes to allow 
voltage to stabilize. The cells and ionizing wires must 
be clean. 

2.  Remove the cover from power box. 
3.  Connect the ground of the high voltage meter to an 

unpainted surface in the power box. 

4.  Check terminals HV1 and HV2 on the power board to 

determine if voltage is present. See Table 3 for 
values. 

5.  If no voltage is present, remove both cells from the 

Air Cleaner and replace door. 
a.  Check the voltage at HV1 and HV2 again. 
b.  If voltage is present, the problem is with one of 

the cells or the wiring to the copper contacts. 

c.  With a flashlight, look into the cabinet to check 

condition of the copper contacts. 

d.  If the contacts are not bent, replace one cell and 

retest voltage. If cell is OK, test the other cell. If 
the problem is with a cell, see Troubleshooting 
Guide. 

e.  If there is no voltage with both cells removed, 

check the power board, APS and transformer to 
make sure that they are functioning correctly. 

6.  If there is voltage present, but the performance light 

does not come on, replace light. 

7.  High voltage can be adjusted with high voltage 

potentiometer if required. See Table 3. 

 
Replacing A Performance Light 

Before replacing the performance light, turn 

OFF

 

power to the Air Cleaner at the source.  
1.  Remove the power box cover. 
2.  Disconnect the performance light wiring connected to 

the LED terminals on the power board. Carefully cut 
the wire ties from the wire bundle. 

WARNING  

Electronic Air Cleaners use high voltage (low 
amperage). Only trained personnel should perform 
service. 

USE CAUTION!

 Electric shock can cause injury 

or death.  

CAUTION  

For most troubleshooting, the cells should be 
removed from the Air Cleaner.

 A short in one of the 

cells will cause the power board to shutdown and the 
performance light will stay off. Unless otherwise directed 
remove the cells from the unit when testing.  

WARNING  

When performing LIVE tests in the power box 

NEVER

 

touch any parts other then what are mentioned in the 
tests. Components carry dangerous voltages and 
extreme care must be taken. 

Содержание ASASD-10

Страница 1: ...ruses and more down to 0 01 micron Dual Voltage Aluminum Collecting Cells are durable and easy to maintain Cell Guide ensures proper placement of collecting cells Activated Carbon Filters remove unple...

Страница 2: ...of electrostatic precipitation Millions of airborne pollutants are carried through the return air ducts of the heating cooling system and treated through four stages of filtration The prefilters 2 re...

Страница 3: ...oss the Air Cleaner will vary with CFM and whether the optional carbon filters have been installed in the unit Location The Air Cleaner must only be installed in the return air duct as close to the fa...

Страница 4: ...pe humidifier must be installed as far from the Air Cleaner as possible 2 Collecting cells must be washed frequently to prevent a mineral deposit build up Installation Location With Air Conditioner Wh...

Страница 5: ...ent direction than the left to right set up The handle should face the door Close access door Wiring Wiring should only be performed by qualified personnel only All wiring must comply with all applica...

Страница 6: ...non chlorine non corrosive non abrasive liquid household detergent Allow detergent to run down both sides of plates and ionizing wires Let stand for 5 minutes or fill up laundry tub with water and DAX...

Страница 7: ...from the power board Measuring High Voltage At Power Board A high voltage meter capable of measuring up to 10 000 VDC is required to test the voltage 1 The Air Cleaner should be ON with the cells ins...

Страница 8: ...oard is turned on and the performance light will come on The light on the power switch will be lit even when the APS is open If the power board fails to come on with the fan on check that the sensor i...

Страница 9: ...voltage meter 9 Replace the power box cover 10 Turn ON the Air Cleaner Setting Approximate Voltage Without High Voltage Meter A high voltage meter should be used to set the high voltage If one is not...

Страница 10: ...ve it from the cabinet 6 If you are removing the power box for any length of time tape a cover over the top opening to prevent air from entering into the system Replacing A Tungsten Ionizing Wire Repl...

Страница 11: ...09 D0 0509 D1 0509 11 Power Box Complete No Cover 12 Carbon Filters Set of 3 1156 3 1156 3 1856 3 1856 3 13 Prefilter R0 0855 R1 0855 R2 0855 R8 0855 14 Cell Guide Plastic R1 0603 R1 0603 R1 0603 R1 0...

Страница 12: ...vely power light and per formance indicator light ON or flashing Cells wet from washing Allow cells to dry completely Particles lodged in cell or broken ionizing wire Wash cell Shake particle out of c...

Страница 13: ...basis for the Air Cleaner to function at its peak efficiency The frequency of cleaning will vary from one house to another On average the cells should be cleaned every 3 months Use the chart below to...

Страница 14: ...NOTES 14...

Отзывы: