Goodman ASASD-10 Скачать руководство пользователя страница 10

 

 

1.  With the ohmmeter set on its lowest scale, take a 

reading between the top center contact of the cell 
and the ionizing fingers on the bottom of the cell. You 
should have continuity. If you do not then there is a 
bad contact between the center contact and the top 
set of ionizing fingers. 

2.  Test the resistance between the top center contact 

and the cell frame. You should read infinite 
resistance. If not, you have a short in the ionizing 
section. 

3.  Take a reading between the two outside contacts on 

the top of the cell. You should have continuity. If you 
do not then there is a bad contact between one of the 
contacts to the live cell plate. Test each top outside 
contact to the last plate in the cell to determine which 
contact is not mating properly. 

4.  Test the resistance between the outside contacts and 

the cell frame. You should read infinite resistance. If 
not you have a short in the collecting section. 

 

Removing Power Box 

1.  Turn the main system switch 

OFF

 or disconnect the 

power cord. 

2.  Remove the power box cover. 
3.  If the unit does not have a cord disconnect the 

source wires to the Air Cleaner. Cap off the wires so 
the system can still be operated. 

4.  Remove the two nuts holding the power box to the 

cabinet.  

5.  Slide the power box forward then up to remove it 

from the cabinet. 

6.  If you are removing the power box for any length of 

time tape a cover over the top opening to prevent air 
from entering into the system. 

 

Replacing A Tungsten Ionizing Wire 

Replacement wires are cut to the correct length and 

have eyelets at each end for easy replacement. 
1. Turn 

OFF

 power to Air Cleaner. 

2.  Remove cell from Air Cleaner. 
3.  Remove all parts of broken wire from the cell. If 

necessary, the cell may be used temporarily with one 
wire missing until a replacement is received. 

4.  Place one end of the loop over the finger at the 

bottom of the cell.  

5.  Using needle-nose pliers, grip the other end of  wire, 

near the bottom of the top loop. Pull the wire up 
toward the top finger. As you apply tension, the 
bottom finger will give, allowing the placement of the 
loop around the top finger. 

6.  Install cell in Air Cleaner. 
7.  Return power to Air Cleaner. 
8.  Test cell for proper operation. 

10 

Fig. 7 — Exploded View 

Use Part Numbers When Ordering (See Separate Parts List) 

# Part 

Description 

1 On/Off 

Switch 

Safety Interlock Switch 

Performance Indicator Light (Green LED) 

Air Proving Switch 

24 Volt Transformer 

6 Power 

Board 

Fibreboard (with 4 Copper Contacts) 

8 Copper 

Contact 

Cord Assembly (Optional) 

10  Lid for Power Box 

11 

Power Box Complete 

12  Carbon Filters (Set of 3) 

13 Prefilter 

14 

Cell Guide (Plastic) 

15 Collecting 

Cell 

16 Cell 

Handle 

17 

Door (with Plastic Clip & Handle) 

18 

Door Handle (Plastic) 

19 Ionizing 

Wire 

20 

Male & Female Door Clip Set 

Содержание ASASD-10

Страница 1: ...ruses and more down to 0 01 micron Dual Voltage Aluminum Collecting Cells are durable and easy to maintain Cell Guide ensures proper placement of collecting cells Activated Carbon Filters remove unple...

Страница 2: ...of electrostatic precipitation Millions of airborne pollutants are carried through the return air ducts of the heating cooling system and treated through four stages of filtration The prefilters 2 re...

Страница 3: ...oss the Air Cleaner will vary with CFM and whether the optional carbon filters have been installed in the unit Location The Air Cleaner must only be installed in the return air duct as close to the fa...

Страница 4: ...pe humidifier must be installed as far from the Air Cleaner as possible 2 Collecting cells must be washed frequently to prevent a mineral deposit build up Installation Location With Air Conditioner Wh...

Страница 5: ...ent direction than the left to right set up The handle should face the door Close access door Wiring Wiring should only be performed by qualified personnel only All wiring must comply with all applica...

Страница 6: ...non chlorine non corrosive non abrasive liquid household detergent Allow detergent to run down both sides of plates and ionizing wires Let stand for 5 minutes or fill up laundry tub with water and DAX...

Страница 7: ...from the power board Measuring High Voltage At Power Board A high voltage meter capable of measuring up to 10 000 VDC is required to test the voltage 1 The Air Cleaner should be ON with the cells ins...

Страница 8: ...oard is turned on and the performance light will come on The light on the power switch will be lit even when the APS is open If the power board fails to come on with the fan on check that the sensor i...

Страница 9: ...voltage meter 9 Replace the power box cover 10 Turn ON the Air Cleaner Setting Approximate Voltage Without High Voltage Meter A high voltage meter should be used to set the high voltage If one is not...

Страница 10: ...ve it from the cabinet 6 If you are removing the power box for any length of time tape a cover over the top opening to prevent air from entering into the system Replacing A Tungsten Ionizing Wire Repl...

Страница 11: ...09 D0 0509 D1 0509 11 Power Box Complete No Cover 12 Carbon Filters Set of 3 1156 3 1156 3 1856 3 1856 3 13 Prefilter R0 0855 R1 0855 R2 0855 R8 0855 14 Cell Guide Plastic R1 0603 R1 0603 R1 0603 R1 0...

Страница 12: ...vely power light and per formance indicator light ON or flashing Cells wet from washing Allow cells to dry completely Particles lodged in cell or broken ionizing wire Wash cell Shake particle out of c...

Страница 13: ...basis for the Air Cleaner to function at its peak efficiency The frequency of cleaning will vary from one house to another On average the cells should be cleaned every 3 months Use the chart below to...

Страница 14: ...NOTES 14...

Отзывы: