INSTALLATION CONSIDERATIONS
14
9.3.3.1 Two Permanent Openings Method.
Two permanent open-
ings, one commencing within 12 in. (300 mm) of the top and one com-
mencing within 12 in. (300 mm) of the bottom, of the enclosure shall be
provided. The openings shall communicate directly, or by ducts, with
the outdoors or spaces that freely communicate with the outdoors, as
follows:
(1)* Where directly communicating with the outdoors or where commu-
nicating to the outdoors through vertical ducts, each opening shall
have a minimum free area of 1 in.
2
/4000 Btu/hr (550 min
2
/kW) of
total input rating of all appliances in the enclosure.
[See Figure
A.9.3.3.1(1)(a) and Figure A.9.3.3.1(1)(b).]
Furnace
Water
Heater
Outlet Air
Chimney or Gas Vent
NOTE: The inlet and outlet air
openings must each have a free
area of not less than one square
inch per 4000 BTU of the
total input rating of all equipment
in the enclosure.
Inlet Air
Ventilation louvers for
unheated crawl space
Alternate
air inlet
Ventilation louvers
(each end of attic)
Figure A.9.3.3.1(1)(a) All Combustion Air From Outdoors -
Inlet Air from Ventilated Crawl Space and Outlet Air
to Ventilated Attic.
Furnace
Water
Heater
Outlet Air
Chimney or Gas Vent
NOTE: The inlet and outlet air
openings must each have a free
area of not less than one square
inch per 4000 BTU of the
total input rating of all equipment
in the enclosure.
Inlet air duct
[ends 1 ft (300 mm)
above floor]
Ventilation louvers
(each end of attic)
Figure A.9.3.3.1(1)(b) All Combustion Air
From Outdoors through Ventilated Attic.
(2)* Where communicating with the outdoors through horizontal
ducts,
e
ach opening shall have a minimum free area of 1 in.
2
/2000 Btu/hr
(1100 min
2
/kW) of total input rating of all appliances in the enclo-
sure.
[See Figure A.9.3.3.1(2).]
Furnace
Water
Heater
Chimney or Gas Vent
NOTE: The air duct openings
must have a free area of not
less than one square inch per
2000 BTU of the total input
rating of all equipment in the
enclosure*.
Outlet air duct
Inlet air duct
Figure A.9.3.3.1(2) All Combustion Air From Outdoors
through Horizontal Ducts.
9.3.3.2* One Permanent Opening Method.
One permanent open-
ings, commencing within 12 in. (300 mm) of the top of the enclosure,
shall be provided. The appliance shall have clearances of at least 1 in.
(25 mm) from the sides and back and 6 in. (150 mm) from the front of
the appliance. The opening shall directly communicate with the out-
doors or shall communicate through a vertical or horizontal duct to the
outdoors or spaces that freely communicate with the outdoors
(see
Figure A.9.3.3.2)
and shall have a minimum free area of the following:
(1) 1 in.
2
/3000 Btu/hr (700 mm
2
per kW) of the total input rating of all
appliances located in the enclosure, and
(2) Not less than the sum of the areas of all vent connectors in the
space.
Furnace
Water
Heater
Opening
Chimney or Gas Vent
NOTE: The single opening must have
a free area of not less than one
square inch per 3000 BTU of
the total input rating of all equip-
ment in the enclosure, but not less than
the sum of the areas of all vent
connectors in the confined space.
Alternate
Opening
Location
Figure A.9.3.3.2 All Combustion Air
From Outdoors through Single Combustion Air Opening.
9.3.4 Combination Indoor and Outdoor Combustion Air.
The use
of a combination of indoor and outdoor combustion air shall be in
accordance with (1) through (3)
(see example calculation in Annex J]:
(1)
Indoor Openings:
Where used, openings connecting the interior
spaces shall comply with 9.3.2.3.
(2)
Outdoor Opening(s) Location.
Outdoor opening(s) shall be lo-
cated in accordance with 9.3.3.
(3)
Outdoor Opening(s) Size.
The outdoor opening(s) size shall be
calculated in accordance with the following:
(a)
The ratio of the interior spaces shall be the available volume
of all communicating spaces divided by the required volume.
(b) The outdoor size reduction factor shall be 1 minus the ratio
of interior spaces.