4.5  TESTING FOR PROPER CIRCUIT BOARD OPERATION

1. Disconnect all AC power from the RV and make sure the generator is OFF.

2. Remove the cover from the ATS sliding a screwdriver blade under the edge of the cover and pry off.

3.  Start the generator and wait 20-45 seconds to see if the relay will energize. If the relay 

does not energize

, go to Step 4. 

If the does energize, but the generator still does not provide 120VAC power to the RV, use an AC Voltmeter to check for 

120VAC at the Normally Open (NO) terminals of the relay. If 120VAC power is present at the NO terminals of the relay, 

there is a wiring issue between the ATS and the RV AC distribution panel. If no voltage is measured on the NO terminals, 

the entire unit will need to be replaced.

4.  With the generator running, use an 

insulated

 screwdriver to carefully push down on the center arm of the relay until the 

center arm of the relay makes contact with the NO contacts of the relay. If AC power is now present in the RV, the circuit 

board in the ATS has failed and must be replaced.

4.6  RELAY CONTRACTS BURNED AND PITTED

If the Relay Contacts are burned and pitted, there is an issue with the generator and its voltage is dropping below 90VAC 

under load. If this problem occurs, you will need to repair or replace the generator and complete ATS.

5. 

HI-POT TESTING

(MANUFACTURING COMPANIES ONLY)

If the hi-pot test is performed from the plug on the power cord, the test may only hi-pot the cord itself; it may not test the RV 

wiring beyond the switch. The hi-pot test should be performed from either the transfer switch output or from the main panel. 

Test as follows:

1. Turn on all circuit breakers in the panel.

2. Make sure the generator is off.

3.  Make sure the power cord is unplugged. Verify that the prongs on the power cord plug are protected so that the hi-pot 

voltage won’t cause a fault reading from a short, or cause bodily injury from electrical shock.

4. Turn off or disconnect all appliances that would be damaged by the hi-pot test.

5. Connect the hi-pot leads to:

a) Transfer switch ground bar

b) Transfer switch output terminals hot 1, hot 2 (if present), and neutral.

6.  Energize the hi-pot and conduct test. This will hi-pot test for leakage (short) between the current-carrying conductors and 

the ground in the entire 120/240 VAC circuitry beyond the transfer switch. In most cases it will also test the power cord 

itself. Turn off the hi-pot. 

7.  Do not test the transfer switch generator input. The hi-pot will damage the time delay control module in the transfer switch. 

If the generator wires to the switch must be checked, disconnect the generator wires from the transfer switch and connect 

hi-pot test leads to the loose wires. Reconnect wires after testing.

8.  If hi-pot test fails, there is a short in the system. The next step is to isolate the location of the short. Turn off the main 

breaker in panel and hi-pot test again. If the test still fails, the fault is between the switch and the panel. Test cord for 

shorted plug. If the test passes, turn on the main breaker, and turn on all branch breakers except one. Retest each branch 

circuit individually until the shorted circuit is isolated. Repair the fault and retest. The hi-pot test is successful when there 

are no more fault indications.

5. HI-POT TESTING

Содержание GP-TS-30

Страница 1: ...nsfer Switch User Manual GP TS 30 2020 Go Power Worldwide Technical Support and Product Information gpelectric com Go Power 201 710 Redbrick Street Victoria BC V8T 5J3 Tel 1 866 247 6527 MOBI_MAN_GP T...

Страница 2: ...formation size install date battery type Product Packaging Please safely store the packing the IC Series was delivered in or recycle the packaging components as outlined below LDPE Low Density Polyeth...

Страница 3: ...ric com page 3 CONTENTS 1 INTRODUCTION 4 2 INSTALLATION 4 3 OPERATIONAL TESTING 7 4 TROUBLESHOOTING 8 5 HI POT TESTING 9 6 GENERATOR NOTE 10 7 MEDICAL APPLIANCES 10 8 CAUTION 10 9 WARNINGS 10 10 WARRA...

Страница 4: ...mpartment designed for storage of flammable liquids such as gasoline 2 3 ELECTRICAL PREPARATION Any numbered knockout on the TS 30 can be used for installation Choose a knockout that will facilitate i...

Страница 5: ...IONS A B 1 Connect the power cord leads to terminal 7 and 8 on the narrow end of the relay these are the normally closed N C contacts See Diagram 1 on page 6 for numbered locations 2 Connect the gener...

Страница 6: ...allow any other supply to dominate the inverter and the inverter output will pass through the normally closed contacts of the switch This allows the inverter to operate only in the absence of the othe...

Страница 7: ...enerator There is a pre programmed 20 30 second delay in the transfer switch The delay is designed to allow the generator a brief warm up period When the delay completes its cycle the switch should en...

Страница 8: ...o drop out at which point the voltage will rise to the pre in rush level The contacts will chatter when the A C compressor kicks in however the voltage may read normal Most meters are not fast enough...

Страница 9: ...hould be performed from either the transfer switch output or from the main panel Test as follows 1 Turn on all circuit breakers in the panel 2 Make sure the generator is off 3 Make sure the power cord...

Страница 10: ...tion may cause arcing In addition the act of turning on a light switch or unplugging the cord on an electrical appliance can cause a spark which can ignite any combustible liquids or vapors Therefore...

Страница 11: ...lting from but not limited to Misuse and or abuse neglect or accident Exceeding the unit s design limits Improper installation including but not limited to improper environmental protection and improp...

Страница 12: ...2020 Go Power Worldwide Technical Support and Product Information gpelectric com Go Power 201 710 Redbrick Street Victoria BC V8T 5J3 Tel 1 866 247 6527 MOBI_MAN_GP TS 30 RevE...

Отзывы: