The Go Power! 30-amp Transfer Switch (TS-30) provides automatic power switching between two separate 120 volt AC 

input sources, including power cords, onboard generators, or onboard inverters. The TS-30 will sense the presence of 

available power supplies and automatically select the proper one.

The TS-30 can be installed at the electrical entry of the RV on the line side of the main distribution panel, or it can be 

installed on the load side of the panel between the main panel and a sub panel, allowing switching for either the entire 

electrical load or only designated circuits.

2. INSTALLATION

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

2.1  DISCONNECT POWER

Make sure the generator is off, the external power cord is unplugged, and the inverter, if any, is shut off.

2.2  MOUNTING LOCATIONS

The TS-30 mounting location may be on any interior surface where the unit will be out of direct weather. The chosen location must 

be accessible after installation is complete to facilitate future servicing. If possible, mount the TS-30 near the power cord entry or the 

location of the generator output. Typical locations include under counter cabinets, below closet compartments, inside the bed pedestal or 

cabinets, overhead cabinets, under-floor storage compartments accessed from the vehicle exterior, etc.

CAUTION: To prevent exposure to foreign contaminants, do not mount the transfer switch in an engine compartment 

under kitchen sink drains or water pipes within the battery compartment or any compartment designed for storage of 

flammable liquids such as gasoline.

2.3  ELECTRICAL PREPARATION

Any numbered knockout on the TS-30 can be used for installation. Choose a knockout that will facilitate installation and service within the 

selected mounting area.

2.4  MOUNTING

Mount the TS-30 with screws through holes provided in bottom corners of the can. The unit should be screwed to a solid surface firmly 

enough to hold its weight during vehicle operation.

2.5  ELECTRICAL CONNECTIONS

1.  Attach an 8-gauge chassis ground wire to the transfer switch ground bar. A direct access hole to the ground bar is provided 

through the enclosure for convenience.

2.  Determine proper connections of wire conductors to electrical terminals. On 120 VAC wiring the ground wire is bare or 

green, the neutral wire is white, and the hot wire is black.

3.  Strip the outer jacket from all of the incoming cables and strip insulation from all ends of the copper conductors. Insert 

cables through clamps in openings. Do not tighten cable clamps at this time.

4.  Route internal ground wires around lower area of enclosure and secure to ground wires away from electrical contacts on 

components to avoid the possibility of electrical short-circuit.

5. Connect the ground wires to the ground bar. Tighten terminals to a minimum of 20 inch-pounds.
6. Connect the neutral (white) wire connections.
7. Connect the hot wire(s) (black).
8.  To connect the wire leads, strip the wire insulation 0.5 inches, insert the bare wire into the vacant hole and drop the lever 

down to secure the wire in the connector. 

9. Tighten cable clamps on switch enclosure.

10. Attach lid. The lid is designed to snap on and should not open without deliberate effort.

1. INTRODUCTION

Содержание GP-TS-30

Страница 1: ...nsfer Switch User Manual GP TS 30 2020 Go Power Worldwide Technical Support and Product Information gpelectric com Go Power 201 710 Redbrick Street Victoria BC V8T 5J3 Tel 1 866 247 6527 MOBI_MAN_GP T...

Страница 2: ...formation size install date battery type Product Packaging Please safely store the packing the IC Series was delivered in or recycle the packaging components as outlined below LDPE Low Density Polyeth...

Страница 3: ...ric com page 3 CONTENTS 1 INTRODUCTION 4 2 INSTALLATION 4 3 OPERATIONAL TESTING 7 4 TROUBLESHOOTING 8 5 HI POT TESTING 9 6 GENERATOR NOTE 10 7 MEDICAL APPLIANCES 10 8 CAUTION 10 9 WARNINGS 10 10 WARRA...

Страница 4: ...mpartment designed for storage of flammable liquids such as gasoline 2 3 ELECTRICAL PREPARATION Any numbered knockout on the TS 30 can be used for installation Choose a knockout that will facilitate i...

Страница 5: ...IONS A B 1 Connect the power cord leads to terminal 7 and 8 on the narrow end of the relay these are the normally closed N C contacts See Diagram 1 on page 6 for numbered locations 2 Connect the gener...

Страница 6: ...allow any other supply to dominate the inverter and the inverter output will pass through the normally closed contacts of the switch This allows the inverter to operate only in the absence of the othe...

Страница 7: ...enerator There is a pre programmed 20 30 second delay in the transfer switch The delay is designed to allow the generator a brief warm up period When the delay completes its cycle the switch should en...

Страница 8: ...o drop out at which point the voltage will rise to the pre in rush level The contacts will chatter when the A C compressor kicks in however the voltage may read normal Most meters are not fast enough...

Страница 9: ...hould be performed from either the transfer switch output or from the main panel Test as follows 1 Turn on all circuit breakers in the panel 2 Make sure the generator is off 3 Make sure the power cord...

Страница 10: ...tion may cause arcing In addition the act of turning on a light switch or unplugging the cord on an electrical appliance can cause a spark which can ignite any combustible liquids or vapors Therefore...

Страница 11: ...lting from but not limited to Misuse and or abuse neglect or accident Exceeding the unit s design limits Improper installation including but not limited to improper environmental protection and improp...

Страница 12: ...2020 Go Power Worldwide Technical Support and Product Information gpelectric com Go Power 201 710 Redbrick Street Victoria BC V8T 5J3 Tel 1 866 247 6527 MOBI_MAN_GP TS 30 RevE...

Отзывы: