4. 

TROUBLESHOOTING

4.1  LOW VOLTAGE

Low voltage is harmful to most appliances. Contactor-based transfer switches are also affected by low voltage; if the voltage 

level drops far enough the contactor points will “chatter”. Sustained contact chattering can cause transfer switch damage. 

Switches that have been damaged by chattering need to be returned to the factory for replacement.

4.2  GENERAL LOW VOLTAGE

Low voltage can be caused by low voltage conditions such as an RV park with inadequate wiring for crowded camper 

conditions where everyone’s electricity suffers (brownout). In this case a voltmeter will be helpful and will show a low voltage 

reading from the park receptacle, even before the RV is plugged in. When you experience general low voltage conditions, 

remember that brownouts can be harmful to most appliances. A better alternative might be to utilize the generator until park 

voltage conditions improve.

4.3  LOCALIZED LOW VOLTAGE

Low voltage conditions can be caused by specific situations such as an additional cord, which is too long and too small for 

the load. Do not attempt to extend the RV power cord by using a 16-gauge 100-foot extension cord, or any cord not rated for 

an RV-size load. A localized low voltage condition will result when a load is turned on which is larger than that which the cord 

is designed for. As soon as the RV tries to draw more current than the amount for which the cord is rated, the voltage will 

fall within the length of the cord, and the RV will experience low voltage. This is especially noticeable during in rush current 

situations such as an air conditioner start-up.

This affects contactor-based transfer switches. The compressor will try to start; the voltage will drop, which will cause the 

contactor to drop out, at which point the voltage will rise to the pre-in rush level. The contacts will chatter when the A/C 

compressor kicks in, however the voltage may read normal. Most meters are not fast enough to record this voltage drop. You 

can test for low voltage readings during this inrush cycle by reading voltage at the contactor terminals while manually holding 

the contactor plunger down in its closed position. This will override the chattering condition and the meter will have time to 

register the reduced voltage. If this condition exists, identify and correct the low voltage situation before proceeding further.

Batteries are capable of providing very large currents in case of a short circuit. If this occurs with no DC overcurrent protection, 

it will result in overheating and melting of the cables and possibly serious injury and/or fire.  

DC overcurrent protection is not included with the IC Series.  It must be installed between the Inverter/Charger and battery 

bank for safety reasons and to comply with code regulations.  

Use a very fast acting DC fuse or circuit breaker in the positive cable, the fuse should be installed as close to possible to 

the battery positive terminal.  Ideally the fuse/circuit breaker should be installed within 18” (45cm of the battery).  The fuse 

required for DC Cable lengths up to 5ft is detailed in the above table.

In all installations a battery disconnect switch is required. If you install a circuit breaker for overcurrent protection this will 

suffice as a disconnect switch.  If you install a fuse for overcurrent protection, then a separate disconnect switch will need 

to be installed.

4.4  PHYSICAL INTERFERENCE

Some transfer switch models have wiring connections made by wire nuts on 6″ leads. Occasionally on these models, the 

wiring connections will get folded into the can in such a manner that the wiring will interfere with the physical operation of 

the relay. Visually inspect for free operation of the relay(s).

4. TROUBLESHOOTING

Содержание GP-TS-30

Страница 1: ...nsfer Switch User Manual GP TS 30 2020 Go Power Worldwide Technical Support and Product Information gpelectric com Go Power 201 710 Redbrick Street Victoria BC V8T 5J3 Tel 1 866 247 6527 MOBI_MAN_GP T...

Страница 2: ...formation size install date battery type Product Packaging Please safely store the packing the IC Series was delivered in or recycle the packaging components as outlined below LDPE Low Density Polyeth...

Страница 3: ...ric com page 3 CONTENTS 1 INTRODUCTION 4 2 INSTALLATION 4 3 OPERATIONAL TESTING 7 4 TROUBLESHOOTING 8 5 HI POT TESTING 9 6 GENERATOR NOTE 10 7 MEDICAL APPLIANCES 10 8 CAUTION 10 9 WARNINGS 10 10 WARRA...

Страница 4: ...mpartment designed for storage of flammable liquids such as gasoline 2 3 ELECTRICAL PREPARATION Any numbered knockout on the TS 30 can be used for installation Choose a knockout that will facilitate i...

Страница 5: ...IONS A B 1 Connect the power cord leads to terminal 7 and 8 on the narrow end of the relay these are the normally closed N C contacts See Diagram 1 on page 6 for numbered locations 2 Connect the gener...

Страница 6: ...allow any other supply to dominate the inverter and the inverter output will pass through the normally closed contacts of the switch This allows the inverter to operate only in the absence of the othe...

Страница 7: ...enerator There is a pre programmed 20 30 second delay in the transfer switch The delay is designed to allow the generator a brief warm up period When the delay completes its cycle the switch should en...

Страница 8: ...o drop out at which point the voltage will rise to the pre in rush level The contacts will chatter when the A C compressor kicks in however the voltage may read normal Most meters are not fast enough...

Страница 9: ...hould be performed from either the transfer switch output or from the main panel Test as follows 1 Turn on all circuit breakers in the panel 2 Make sure the generator is off 3 Make sure the power cord...

Страница 10: ...tion may cause arcing In addition the act of turning on a light switch or unplugging the cord on an electrical appliance can cause a spark which can ignite any combustible liquids or vapors Therefore...

Страница 11: ...lting from but not limited to Misuse and or abuse neglect or accident Exceeding the unit s design limits Improper installation including but not limited to improper environmental protection and improp...

Страница 12: ...2020 Go Power Worldwide Technical Support and Product Information gpelectric com Go Power 201 710 Redbrick Street Victoria BC V8T 5J3 Tel 1 866 247 6527 MOBI_MAN_GP TS 30 RevE...

Отзывы: