30 Amp Transfer Switch

User Manual

GP-TS-30

© 2020 Go Power!

Worldwide Technical Support and Product Information 

gpelectric.com

Go Power!

201-710 Redbrick Street Victoria, BC, V8T 5J3

Tel: 1.866.247.6527

MOBI_MAN_GP-TS-30-RevE

Содержание GP-TS-30

Страница 1: ...nsfer Switch User Manual GP TS 30 2020 Go Power Worldwide Technical Support and Product Information gpelectric com Go Power 201 710 Redbrick Street Victoria BC V8T 5J3 Tel 1 866 247 6527 MOBI_MAN_GP T...

Страница 2: ...formation size install date battery type Product Packaging Please safely store the packing the IC Series was delivered in or recycle the packaging components as outlined below LDPE Low Density Polyeth...

Страница 3: ...ric com page 3 CONTENTS 1 INTRODUCTION 4 2 INSTALLATION 4 3 OPERATIONAL TESTING 7 4 TROUBLESHOOTING 8 5 HI POT TESTING 9 6 GENERATOR NOTE 10 7 MEDICAL APPLIANCES 10 8 CAUTION 10 9 WARNINGS 10 10 WARRA...

Страница 4: ...mpartment designed for storage of flammable liquids such as gasoline 2 3 ELECTRICAL PREPARATION Any numbered knockout on the TS 30 can be used for installation Choose a knockout that will facilitate i...

Страница 5: ...IONS A B 1 Connect the power cord leads to terminal 7 and 8 on the narrow end of the relay these are the normally closed N C contacts See Diagram 1 on page 6 for numbered locations 2 Connect the gener...

Страница 6: ...allow any other supply to dominate the inverter and the inverter output will pass through the normally closed contacts of the switch This allows the inverter to operate only in the absence of the othe...

Страница 7: ...enerator There is a pre programmed 20 30 second delay in the transfer switch The delay is designed to allow the generator a brief warm up period When the delay completes its cycle the switch should en...

Страница 8: ...o drop out at which point the voltage will rise to the pre in rush level The contacts will chatter when the A C compressor kicks in however the voltage may read normal Most meters are not fast enough...

Страница 9: ...hould be performed from either the transfer switch output or from the main panel Test as follows 1 Turn on all circuit breakers in the panel 2 Make sure the generator is off 3 Make sure the power cord...

Страница 10: ...tion may cause arcing In addition the act of turning on a light switch or unplugging the cord on an electrical appliance can cause a spark which can ignite any combustible liquids or vapors Therefore...

Страница 11: ...lting from but not limited to Misuse and or abuse neglect or accident Exceeding the unit s design limits Improper installation including but not limited to improper environmental protection and improp...

Страница 12: ...2020 Go Power Worldwide Technical Support and Product Information gpelectric com Go Power 201 710 Redbrick Street Victoria BC V8T 5J3 Tel 1 866 247 6527 MOBI_MAN_GP TS 30 RevE...