GFY recommends 600v 12 ga stranded wire for all 3 phase GFY installations.
•
GFY recommends 600v 12 ga stranded wire for all 1 phase GFY installations.
•
Size of input and output wires may go up based on length and current draw of VFD and motor.
•
See Power Requirements (page after next) for current draw of VFD and motor.
VFD = Variable Frequency Drive
A separate insulated ground must be provided to each
VFD from the electrical panel.
Motor is rated with an Insulation Class H or F;
Ensure proper wiring is used as per current electrical codes.
Wet/Agricultural - PVC Conduit
Dry (Industrial/Commercial) - EMT Conduit
3 Phase = (3) 12g Wires + Insulated
Ground 1 Phase = (2) 12g Wires + Insulated
Ground
Electric Panel
VFD
Motor
3 phase installations
require minimum
12g stranded wire.
Single phase installations
require minimum
12g stranded wire.
AC(PWM) 3ph
with 12g wires.
***NOTE*** This run MUST be stranded
cable.
Do NOT use solid cable.
Wet/Agricultural - PVC Conduit
3 Phase = shielded cable, inverter-rated,
(3) 12g Wires + Insulated Ground
Dry (Industrial/Commercial) - EMT
Conduit 3 Phase = (3) 12g Wires +
Insulated Ground
Wire Requirements
|