19
4.
Once the system operation has been checked to be satisfactory, the voltage control may be set
to its maximum value. This will provide enough voltage for stable operation when running at
high current settings.
5.2
Field Control Operation
The necessity to use calibration curves can be avoided by using a field controller to sense the
magnetic field and provide a corresponding power supply control signal through the power supply
programming inputs. Contact GMW for suitable instrumentation and software (Labview)
([email protected]).
6. MAINTENANCE
Whenever performing maintenance on this magnet all electrical plug socket
disconnects must be disconnected and a plug lockout device used to properly shut down
the electrical system. Refer to the lockout/tagout procedure defined in section 1.3.
6.1
Cooling Circuit
Check the cooling water circuit to ensure the water is clean and free of debris and bacterial growth.
If an in-line water filter is used, ensure that the filter is clean. If this magnet is used in conjunction
with a closed cycle chiller please refer to the chillers' User Manual for details specific to that chiller
for cleaning and maintenance.
For closed loop water chilling systems we recommend treating the water for algae and corrosion as
required, but no less than every six months. Thermo Fisher provides a water treatment kit, part
number 610000000005, which consists of a corrosion & scale inhibitor, and a biocide. This kit will
treat 10 gallons of water, and multiple kits may be required depending on the cooling system
capacity. Further information regarding water treatment can be found at the end of the 'Technical
Reference' section of this manual.
6.2
Electrical Connections
Ensure that all electrical connections are tight. Check that the cable insulation is undamaged and
that the cable assembly is properly strain relieved. Ensure that all electrical terminal covers are in
place and are firmly secured.
6.3
Interlock Testing
Interlock functions should be verified no less than every three months. Use the procedure described
in Section 4 - 'Interlock Testing' to test the interlock functions.
6.4
Spare Parts and Consumables
Содержание 5203
Страница 2: ...Blank Page ...
Страница 11: ...9 2 3 11907 0224 0 5203 General Assembly ...
Страница 12: ...10 2 4 11907 0233 0 5203 Terminal Block Assembly ...
Страница 13: ...11 2 5 17907 0412 0 5203 Mounting Plate ...
Страница 24: ...22 9 EXCITATION CURVES AND FIELD UNIFORMITY Excitation Curves for the various pole types ...
Страница 25: ...23 Excitation and Field Remanence for the standard pole Type A ...
Страница 26: ...24 Near and far vertical field profiles for the standard pole Type A ...
Страница 27: ...25 ...
Страница 28: ...26 ...
Страница 39: ...37 10 TEST DATA ...
Страница 41: ...39 13907 0025 1 System Wiring 5203 1x BOP20 50 and PDU ...
Страница 42: ...40 13907 0026 1 System Wiring 5203 2x BOP20 50 and PDU ...
Страница 43: ...41 1C907 5203 08 Electrical Assembly 5203 and IECO BPS ...
Страница 44: ...42 1D907 5203 08 Electrical Wiring 5203 and IECO BPS ...
Страница 45: ...43 1C907 5203 09 Electrical Assembly 5203 IECO BPS and 5972 ...
Страница 46: ...44 1D907 5203 09 Electrical Wiring 5203 IECO BPS and 5972 ...
Страница 48: ...46 16907 0116 1 S1 Cable Current Interlock 5203 BOP20 50 and PDU ...
Страница 49: ...47 16907 0116 3 S1 Cable Current Interlock 5203 IECO BPS and 5972 ...
Страница 50: ...48 16907 0281 0 Cable Assembly Interlock Pigtail 5972 or IECO BPS ...
Страница 51: ...49 11907 0620 0 GMW RC 1920 Equipment Rack ...
Страница 57: ...BPS 40 100 Bipolar Power Supply BPS 40 100 40V 100A International Electric Co Document 200203PHa 3 2 2020 ...
Страница 65: ...ThermoFlex Preventative Maintenance ...