AP-134
Thermo Scientific Cooling Water System:
Cleaning/Flushing Procedures
Analytical Procedure
PRE-SHIP TEST/PASSIVATE FOR
ORIGINAL EQUIPMENT
MANUFACTURERS
Purpose
If equipment testing is conducted prior to
shipping or storage, new cooling water
systems should be flushed and passivated.
Passivation helps to minimize corrosion and
prepares the metal surface for the corrosion
inhibitors in the treatment program. The
following procedure will passivate
metal surfaces and improve system
performance and reliability.
Procedure
1. Confirm the unit is ready for operation.
2. Fill the cooling water system with
deionized (DI), distilled or Reverse
Osmosis (RO) water and circulate for
several minutes. Repair any leaks before
proceeding.
3. Add the contents of the bottle labeled
460-Thermo100; circulate for 10-15
minutes.
4. Add the contents of the bottle labeled
NALCO 7330; circulate until pre-ship
testing is complete, but no less than a
minimum of 4 hours.
5. Drain the system completely.
6. Attach the Fluid Replacement Reminder
sticker to a prominent location on the unit.
Sign and date the sticker noting when the
system was treated and a scheduled date
for the next treatment.
7. The unit is now ready for shipment or
storage.
For more information, please contact the
Inside Sales Department at
(800) 258-0830.
Содержание 5203
Страница 2: ...Blank Page ...
Страница 11: ...9 2 3 11907 0224 0 5203 General Assembly ...
Страница 12: ...10 2 4 11907 0233 0 5203 Terminal Block Assembly ...
Страница 13: ...11 2 5 17907 0412 0 5203 Mounting Plate ...
Страница 24: ...22 9 EXCITATION CURVES AND FIELD UNIFORMITY Excitation Curves for the various pole types ...
Страница 25: ...23 Excitation and Field Remanence for the standard pole Type A ...
Страница 26: ...24 Near and far vertical field profiles for the standard pole Type A ...
Страница 27: ...25 ...
Страница 28: ...26 ...
Страница 39: ...37 10 TEST DATA ...
Страница 41: ...39 13907 0025 1 System Wiring 5203 1x BOP20 50 and PDU ...
Страница 42: ...40 13907 0026 1 System Wiring 5203 2x BOP20 50 and PDU ...
Страница 43: ...41 1C907 5203 08 Electrical Assembly 5203 and IECO BPS ...
Страница 44: ...42 1D907 5203 08 Electrical Wiring 5203 and IECO BPS ...
Страница 45: ...43 1C907 5203 09 Electrical Assembly 5203 IECO BPS and 5972 ...
Страница 46: ...44 1D907 5203 09 Electrical Wiring 5203 IECO BPS and 5972 ...
Страница 48: ...46 16907 0116 1 S1 Cable Current Interlock 5203 BOP20 50 and PDU ...
Страница 49: ...47 16907 0116 3 S1 Cable Current Interlock 5203 IECO BPS and 5972 ...
Страница 50: ...48 16907 0281 0 Cable Assembly Interlock Pigtail 5972 or IECO BPS ...
Страница 51: ...49 11907 0620 0 GMW RC 1920 Equipment Rack ...
Страница 57: ...BPS 40 100 Bipolar Power Supply BPS 40 100 40V 100A International Electric Co Document 200203PHa 3 2 2020 ...
Страница 65: ...ThermoFlex Preventative Maintenance ...