D5034 

- SIL 3 Switch/Proximity Interface 

G.M. International ISM0113-7 

Parameters Table 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Device Parameters 

D5034 Associated 

Apparatus Parameters 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Cable Parameters 

Uo / Voc = 10.5 V 

Ui / Vmax 

In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check 
its suitability for the Hazardous Area/Hazardous Locations and group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded 
by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5034 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, 
Check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the 
effective group. See parameters indicated in the table below: 

D5034 Terminals 

Ch1 
Ch2 

7 - 8 

9 - 10 

Ch1 
Ch2 

7 - 8 

9 - 10 

Io / Isc = 15 mA 

Ch1 
Ch2 

7 - 8 

9 - 10 

Po / Po = 39 mW 

 

Ii/ Imax 

 

Pi / Pi 

 

D5034 Terminals 

D5034 Associated Apparatus 

Parameters Cenelec (US) 

Ci / Ci  C cable 

 

IIC (A, B) 

Co / Ca = 2.4 µF 

Co / Ca = 16.8 µF 

Co / Ca = 75 µF 

IIB (C) 
IIA (D) 

For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable), 
then 50 % of Co and Lo parameters are applicable and shall not be exceeded 

(50 % of the Co and Lo become the limits which must include the cable such that 

Ci C cable 

 50 % of Co and Li  L cable 

 50 % of Lo). 

If the cable parameters are unknown, the following value may be used: Capacitance 180pF per meter (60pF per foot), Inductance 0.60µH per meter (0.20µH per foot). 

 

Co / Ca = 66 µF 

Co / Ca = 16.8 µF 

IIIC (E, F, G) 

Ch1 

Ch2 

7 - 8 

9 - 10 

Li / Li L cable 

 

IIC (A, B) 

Lo / La = 163 mH 
Lo / La = 652 mH 

Lo / La = 1300 mH 

IIB (C) 
IIA (D) 

Lo / La = 2140 mH 

Lo / La = 652 mH 

IIIC (E, F, G) 

Ch1 

Ch2 

7 - 8 

9 - 10 

Li / Ri device and 

L cable / R cable 

 

IIC (A, B) 

Lo / Ro = 918.2 µH/

 

Lo / Ro = 3672.9 µH/

 

Lo / Ro = 7345.8 µH/

 

IIB (C) 
IIA (D) 

Lo / Ro = 12051.8 µH/

 

Lo / Ro = 3672.9 µH/

 

IIIC (E, F, G) 

Ch1 

Ch2 

7 - 8 

9 - 10 

Содержание D5034S

Страница 1: ...D5034 SIL 3 Switch Proximity Interface G M International ISM0113 7 SIL 3 Switch Proximity Interface DIN Rail and Termination Board Models D5034S D5034D D5034S D5034D INSTRUCTION SAFETY MANUAL...

Страница 2: ...to max supply change Load influence 0 05 of full scale for a 0 to 100 load resistance change Temperature influence 0 03 of full scale on zero and span for a 1 C change Compatibility CE mark compliant...

Страница 3: ...TR n 898 NEPSI T V Certifications T V Functional Safety Certification Type Approval Certificate DNV and KR for maritime applications High Density two channels per unit Simplified installation using s...

Страница 4: ...ve group See parameters indicated in the table below D5034 Terminals Ch1 Ch2 7 8 9 10 Ch1 Ch2 7 8 9 10 Io Isc 15 mA Ch1 Ch2 7 8 9 10 Po Po 39 mW Ii Imax Pi Pi D5034 Terminals D5034 Associated Apparatu...

Страница 5: ...ector Power Bus PLC In 1 Proximity voltage free Contact In 2 Proximity voltage free Contact voltage free Contact voltage free Contact R1 R2 R1 R2 MODEL D5034S 5 6 1 2 7 8 mA Out SIL 3 RL PLC Terminati...

Страница 6: ...at causes the output signal to go above 7 mA as short circuit of input Assuming that the application program in the safety logic solver is configured to detect High failure and does not automatically...

Страница 7: ...field in order to go to open connection condition equivalent to line breakage and verify that the output current of the repeater reaches low current value 0 35 mA This tests for possible quiescent cur...

Страница 8: ...ew terminal blocks which can be plugged in out into a powered unit without suffering or causing any damage for Zone 2 installations check the area to be nonhazardous before servicing The wiring cables...

Отзывы: