SIL 3 according to IEC 61508:2010 Ed. 2 for Tproof = 1 / 10 yrs (
≤
10% / >10 % of total SIF).
SIL 2 according to IEC 61508:2010 Ed. 2 for Tproof = 17 / 20 yrs (
≤
10% / >10 % of total SIF).
PFDavg (1 year) 5.65 E-05, SFF 90.86 %.
Systematic capability SIL 3
2 fully independent channels.
Input from Zone 0 (Zone 20), installation in Zone 2.
Transparent mode operation.
Field open and short circuit detection available to the PLC/DCS card.
Input and Output short circuit proof
High Accuracy.
Three port isolation, Input/Output/Supply.
EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
ATEX, IECEx, UL & C-UL, FM, FMC, INMETRO, EAC-EX, UKR TR n. 898, NEPSI, TÜV Certifications.
TÜV Functional Safety Certification.
Type Approval Certificate DNV and KR for maritime applications.
High Density, two channels per unit.
Simplified installation using standard DIN-Rail and plug-in terminal blocks, with or without Power Bus, or customized Termination Boards.
250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.
+ Input Ch 1 for Proximity or Voltage free Contact
Terminal block connections
HAZARDOUS AREA
SAFE AREA
- Input Ch 1 for Proximity or Voltage free Contact
+ Input Ch 2 for Proximity or Voltage free Contact
- Input Ch 2 for Proximity or Voltage free Contact
7
8
9
10
+ Output Ch 1
1
- Output Ch 1
2
+ Output Ch 2
3
- Output Ch 2
4
+ Power Supply 24 Vdc
5
- Power Supply 24 Vdc
6
7 8
9 10
2
1
4 3
6 5
Model:
D5034
1 channel
S
2 channels
D
Power Bus and DIN-Rail accessories:
Connector JDFT049
Cover and fix MCHP196
Terminal block male MOR017