D5034 

- SIL 3 Switch/Proximity Interface 

G.M. International ISM0113-7 

D5034 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4, 
Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb –40 to +70 °C, and connected to equipment with a maximum limit for 
AC power supply Um of 250 Vrms. 
Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground. 
D5034 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. IEC/EN60079-14 
Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care 
shall be given to segregation and clear identification of I.S. conductors from non I.S. ones. 
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous. 

Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. 
Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous. 

Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. 
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. 
Any unauthorized modification must be avoided. 

 

Warning 

Operation 

 The single and dual channel Switch/Proximity Interface, D5034S and D5034D is a high integrity repeater, designed to interface contacts or proximity detectors (EN60947-5-6, NAMUR) 
located in Hazardous Area and is suitable for applications requiring SIL 3 level (according to IEC 61508:2010 Ed. 2) in safety related systems for high risk industries. 
Field loop integrity and status (line plus contact or proximitor) are continuously and directly monitored, in transparent mode, into the PLC, ESD, DCS using their existing input line, 
without requiring an additional channel for line fault detection. 
PLC / DCS can detect the following conditions: 

0.5 to 1.3 mA 

Input open condition 

2.0 to 6.0 mA 

Input close condition 

0 to 0.4 mA 

Input fault condition (Line break) 

6.5 to 8.0 mA 

Input fault condition (Short circuit) 

These are automatically detected for proximity switches inputs. A “POWER ON” green led for each channel lits when input power is present. 
 

Note:

 use of voltage free electrical contacts with fault detection enabled (control equipment) requires, near the switch at the end of the line a R1=1 K

 typical (470 

 to 2 K

 range) 

resistor in series and a R2=10 k

 typical (5 K

 to 15 K

 range) resistor in parallel to the contacts in order to allow the fault detection circuit to distinguish between a condition of 

contact close/open and a line open/short circuit fault. 

Installation 

 D5034 series are Switch/Proximity Detector Interface housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or 
on customized Termination Board. 
D5034 unit can be mounted with any orientation over the entire ambient temperature range. 
Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without 
suffering or causing any damage 

(for Zone 2 installations check the area to be nonhazardous before servicing)

The wiring cables have to be proportionate in base to the current and the length of the cable. 
On the section “Function Diagram” and enclosure side a block diagram identifies all connections. 
Identify the number of channels of the specific card (e.g. D5034S is a single channel model and D5034D is a dual channel model), the function and location of each connection terminal 
using the wiring diagram on the corresponding section, as an example: 
Connect 24 Vdc power supply positive at terminal “5” and negative at terminal “6”. 
For Model D5034S connect positive output of channel 1 at terminal “1” and negative output at “2”. 
For Model D5034D in addition to channel 1 connections above, connect positive output of channel 2 at terminal “3” and negative output at “4”. 
For Model D5034S, in case of Proximity or Voltage free Contact, connect the wires at terminal “7” for positive and “8” for negative. 
For Model D5034D in addition to channel 1 connections above, connect terminal “9” for positive and “10” for negative on channel 2. 
 
Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 
Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other 
and do not produce any unintentional connection. 
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation 
requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. 
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. 
If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water. 

Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5034 must be cleaned only with a damp or antistatic cloth. 

Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. 
According to EN61010, D5034 series must be connected to SELV or SELV-E supplies. 

 

 

End of Line Resistor for Contact 

 

 

Start-up 

 Before powering the unit check that all wires are properly connected, particularly supply conductors and their polarity, input and output wires, also check that Intrinsically Safe conductors 
and cable trays are segregated (no direct contacts with other non I.S. conductors) and identified either by color coding, preferably blue, or by marking. Check conductors for exposed 
wires that could touch each other causing dangerous unwanted shorts. Turn on power, the “power on” green leds must be lit output condition must be in accordance with condition of the 
corresponding input line. If possible close and open input lines one at time checking the corresponding reflected current output to be correct. 

 

Use of voltage free electrical contacts with fault detection enabled (control equipment) requires, near the switch at the end of the line a 1 K

 typical (470 

 to 2 K

 range) series 

connected resistor and a 10 K

 typical (5 K

 to 15 K

 range) parallel connected resistor in order to allow the fault detection circuit to distinguish between a condition of contact 

close/open and a line open/short circuit fault. 

1 K

 

10 K

 

Содержание D5034S

Страница 1: ...D5034 SIL 3 Switch Proximity Interface G M International ISM0113 7 SIL 3 Switch Proximity Interface DIN Rail and Termination Board Models D5034S D5034D D5034S D5034D INSTRUCTION SAFETY MANUAL...

Страница 2: ...to max supply change Load influence 0 05 of full scale for a 0 to 100 load resistance change Temperature influence 0 03 of full scale on zero and span for a 1 C change Compatibility CE mark compliant...

Страница 3: ...TR n 898 NEPSI T V Certifications T V Functional Safety Certification Type Approval Certificate DNV and KR for maritime applications High Density two channels per unit Simplified installation using s...

Страница 4: ...ve group See parameters indicated in the table below D5034 Terminals Ch1 Ch2 7 8 9 10 Ch1 Ch2 7 8 9 10 Io Isc 15 mA Ch1 Ch2 7 8 9 10 Po Po 39 mW Ii Imax Pi Pi D5034 Terminals D5034 Associated Apparatu...

Страница 5: ...ector Power Bus PLC In 1 Proximity voltage free Contact In 2 Proximity voltage free Contact voltage free Contact voltage free Contact R1 R2 R1 R2 MODEL D5034S 5 6 1 2 7 8 mA Out SIL 3 RL PLC Terminati...

Страница 6: ...at causes the output signal to go above 7 mA as short circuit of input Assuming that the application program in the safety logic solver is configured to detect High failure and does not automatically...

Страница 7: ...field in order to go to open connection condition equivalent to line breakage and verify that the output current of the repeater reaches low current value 0 35 mA This tests for possible quiescent cur...

Страница 8: ...ew terminal blocks which can be plugged in out into a powered unit without suffering or causing any damage for Zone 2 installations check the area to be nonhazardous before servicing The wiring cables...

Отзывы: