4.1.5.3 Setting Battery Type
WAIT
KW
KW
KW
KW
KW
KWh
INVERTER EXPERT
EOUT
TYP
Figure 33 Battery type setting
TYP refers to battery type , 00 is referring to lithium battery; please set TYP as 01 when
the battery type is lead-acid.
The default battery type is lithium-ion,press”OK” button and input the corresponding
battery type code to modify. Press “OK” to finish the setting and you will enter the
setting interface as shown in Figure 34.
4.1.5.4 Setting Battery Charging Cut-off Voltage
WAIT
KW
KW
KW
KW
KW
KWh
INVERTER EXPERT
EOUT
BVH
V
Figure 34 Battery charging cut-off voltage setting
BVH refers to battery charging cut-off voltage. The BVH setting range is 40V-60V, the default
value is 54V.Please set the voltage according to the battery recommended value for different
battery types.
Press “OK” to modify setting on this parameter. Make sure the BVH value input here is higher
than the BVL value setting Section 4.1.5.5. Press “OK” to finish this setting and you will enter the