Global Mainstream Dynamic Energy Technology Ltd.
- 28 -
User Manual
GHESS 3.7-4.8-SL hybrid system
Table 13 LCD parameter settings
Note: the LCD background light will be turned off if no actions within 2 minutes.
Please turn on the DC-switch or get the grid connected with the Soldate3700TL, wait until the
LCD is displaying the interface as shown in Figure 30. Long pressing “OK” button for 3 seconds on
the display menu to enter into setting menu, the password input interface as Figure 31 will be
displayed.
WAIT
KW
KW
KW
KW
KW
KWh
INVERTER EXPERT
EOUT
PV1
Figure 30 Display menu
Id
Max discharging current(default 50A)
Ic
Max charging current(default 50A)
CER
Certification
00
G83(default)
01
VDE 0126/4105
02
AS4777
CNY
PV
connection
01
Only PV1
02
Only PV2
03
PV independent (default)
04
PV parallel
MDE
Operation
mode
00
PV self of use(default)
01
Forced Time of Use(TOU)
00charging time
01discharging time
02
Back up reserved
04
Slave mode
ADR
Meter address(001-255)
CT
Current transformer(01-99)
BMS
01
Pylon
Communication mode: RS485
SOC
Discharging stop capacity (default 20%)
FED
Grid feed-in power XXXX%(3600*x%)X default 100
RST
Restore to the default factory setting(RST1111)