PM 1001484 000 06
Device handbook SINEAX DM5000
72/87
B Display matrices
B0 Used abbreviations for the measurements
Instantaneous values
Name
Measurement identification
Unit
Description
U
U
TRMS
V
Voltage system
U1N
U
1N
TRMS
V
Voltage between phase L1 and neutral
U2N
U
2N
TRMS
V
Voltage between phase L2 and neutral
U3N
U
3N
TRMS
V
Voltage between phase L3 and neutral
U12
U
12
TRMS
V
Voltage between phases L1 and L2
U23
U
23
TRMS
V
Voltage between phases L2 and L3
U31
U
31
TRMS
V
Voltage between phases L3 and L1
UNE
U
NE
TRMS
V
Zero displacement voltage 4-wire systems
I
I
TRMS
A
Current system
I1
I
1
TRMS
A
Current phase L1
I2
I
2
TRMS
A
Current phase L2
I3
I
3
TRMS
A
Current phase L3
IN
I
N
TRMS
A
Neutral current
IPE
I
PE
TRMS
Earth current
P
P
TRMS
W
Active power system (P=P1+P2+P3)
P1
P
1
TRMS
W
Active power phase L1
P2
P
2
TRMS
W
Active power phase L2
P3
P
3
TRMS
W
Active power phase L3
Q
Q
TRMS
var
Reactive power system (Q=Q1+Q2+Q3)
Q1
Q
1
TRMS
var
Reactive power phase L1
Q2
Q
2
TRMS
var
Reactive power phase L2
Q3
Q
3
TRMS
var
Reactive power phase L3
S
S
TRMS
VA
Apparent power system
S1
S
1
TRMS
VA
Apparent power phase L1
S2
S
2
TRMS
VA
Apparent power phase L2
S3
S
3
TRMS
VA
Apparent power phase L3
F
F
TRMS
Hz
System frequency
PF
PF
TRMS
Active power factor P/S
PF1
PF
1
TRMS
Active power factor P1/S1
PF2
PF
2
TRMS
Active power factor P2/S2
PF3
PF
3
TRMS
Active power factor P3/S3
QF
QF
TRMS
Reactive power factor Q / S
QF1
QF
1
TRMS
Reactive power factor Q1 / S1
QF2
QF
2
TRMS
Reactive power factor Q2 / S2
QF3
QF
3
TRMS
Reactive power factor Q3 / S3
LF
LF
TRMS
Load factor system
LF1
LF
1
TRMS
Load factor phase L1
LF2
LF
2
TRMS
Load factor phase L2
LF3
LF
3
TRMS
Load factor phase L3
UR1
U
pos
SEQ
V
Positive sequence voltage
UR2
U
neg
SEQ
V
Negative sequence voltage
U0
U
zero
SEQ
V
Zero sequence voltage
IR1
I
pos
SEQ
A
Positive sequence current
IR2
I
neg
SEQ
A
Negative sequence current
I0
I
zero
SEQ
A
Zero sequence current
UR2R1
U
neg/pos
UNB
%
Unbalance factor voltage UR2/UR1
IR2R1
I
neg/pos
UNB
%
Unbalance factor current IR2/IR1
U0R1
U
zero/pos
UNB
%
Unbalance factor voltage U0/UR1
I0R1
I
zero/pos
UNB
%
Unbalance factor current I0/IR1
IMS
I
-
+
ø
TRMS
A
Average current with sign of P