PM 1001484 000 06
Device handbook SINEAX DM5000
37/87
6.4.6
Resetting the communication settings
If the communication settings of the Standard
interface are no longer known, they can be
reset to the default settings by pressing the
sunk-in reset button (located below the
operating LED) for at least 3s. During the reset
the operating LED flashes red. After the reset
the device is rebooted.
6.5 Simulation of analog / digital outputs
To check if subsequent circuits will work properly with output values provided by the device, using the
service menu
Simulation
all analog or digital / relay outputs may be simulated. This is done by either
entering analog output values or selecting discrete states for the digital outputs / relays.
When output simulation is turned on, the device configuration will be changed. This may take a few
seconds. Once the simulation is turned off, the device is switched off or the menu selection is changed,
the device goes back to its initial configuration.
Simulation is possible via webpage and as well via the local display.
Simulation of digital outputs via device webpage