7.6.2 Monitoring fault-currents
Each (optional) fault current module provides
two channels
for monitoring residual or fault current. For
each of the channels an alarm and a prewarning limit can be defined, which can be used as follows:
… Activating a
when the alarm limit is violated or a breakage occurs (2mA input only)
… as source for digital outputs
… Entry into the alarm list, if the state of the alarm limits monitoring changes or when a breakage
occurs (2mA input only)
… Entry into the event list, if the state of the prewarning limits monitoring changes
… the value of the individual fault currents can also be output via the analog outputs
The present values of the monitored fault currents are visible via the menu of the instantaneous values:
Meaning of the used symbols
Current value normal
Prewarning limit violated
Alarm limit violated
Alarm: Configured limit for ON
Alarm: Configured limit for OFF
Prewarning: Configured limit for ON
Prewarning: Configured limit for OFF
Breakage of measurement line detected