D1130 

- SIL 2 Switch / Proximity Detector Repeater Relay Output 

G.M. International ISM0048-12 

D1130 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN Rail located in Safe Area/Non Hazardous Locations or Zone 2, Group IIC, 
Temperature Classification T4, Class I, Division 2, Groups A, B, C, D, Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA Temperature Code T4 Hazardous Area/Hazardous  
Locations (according to EN/IEC60079-15, FM Class No. 3611, CSA-C22.2 No. 213-M1987, CSA-E60079-15) within the specified operating temperature limits Tamb -20 to +60 °C, and 
connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. 

Non-incendive field wiring is not recognized by the Canadian Electrical Code, installation is permitted in the US only. 
For installation of the unit in a Class I, Division 2 or Class I, Zone 2 location, the wiring between the control equipment and the D1130 associated apparatus shall be accomplished 
via conduit connections or another acceptable Division 2, Zone 2 wiring method according to the NEC and the CEC. 
Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground. 
D1130 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards 
(e.g. IEC/EN60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165, 
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505, 
Canadian Electrical Code CEC) following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones. 
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area/Hazardous Locations or 
unless area is known to be nonhazardous. 

Warning: substitution of components may impair Intrinsic Safety and suitability for Division 2, Zone 2. 
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock 
when connected to live hazardous potential. 
Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous. 

Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. 
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided. 

 

Warning 

 

D1130 Associated Apparatus

FM Approved

under Entity Concept

and non-incendive field wiring

Unclassified Locations or

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D, T-Code T4

Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4

FM Approved under Entity Concept,

or third party approval

Hazardous (Classified) Locations

Class I, Division 1, Groups A, B, C, D

Class II, Division 1, Groups E, F, G

Class III, Division 1

Class I, Zone 0, Group IIC, IIB, IIA

Intrinsically 

Safe Equipment

Must not use or generate

more than 250 Vrms or Vdc

Control 

Equipment

Unclassified Locations

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D

Class II, Division 2, Groups E, F, G

Class III, Division 2

Class I, Zone 2, Group IIC, IIB, IIA

FM Approved under non-incendive field

wiring (permitted only for US installations),

or third party approval

13
14

1
2

+

-

Power Supply

3 L/+

4 N/-

16

15

-

+

Intrinsically 

Safe Equipment

Unclassified Locations or

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D, T-Code T4

Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4

Unclassified Locations

Must not use or generate

more than 250 Vrms or Vdc

8

Control 

Equipment

7

6

5

+

Non-incendive

Equipment

Non-incendive

Equipment

+

-

-

1

13

16

15

14

7

6

5

8

2

Control 

Equipment

Power Supply

Control 

Equipment

D1130 Associated Apparatus

FM Approved

under Entity Concept

and non-incendive field wiring

3 L/+

4 N/-

Testing procedure at T-proof 

The proof test shall be performed to reveal dangerous faults which are undetected by diagnostic. This means that it is necessary to specify how dangerous undetected fault, 
which have been noted during the FMEDA, can be revealed during proof test. 
Note for switch input: use of voltage free electrical contacts with fault detection enabled requires, near the switch at the end of the line, a 1 K

 series connected resistor and a 10 K

  

 

 

    parallel connected resistor in order to allow the fault detection circuit to distinguish between a condition of contact close/open and a line open/short circuit fault. 

The Proof test

 consists of the following steps: 

Steps

 

Action

 

Bypass the Safety PLC or take any other appropriate action to avoid a false trip. 

Vary the state conditions of the input sensors / contacts coming from field and verify that the relay or transistor outputs change their state from energized  

to de-energized and vice-versa; also check that the de-energized state condition corresponds to the required Safety Function. 

Disconnect the input wiring coming from the field sensor / contact and check that the corresponding alarm output is de-energized. 

Short the input connections and verify that the corresponding outputs remains de-energized. In both cases, the corresponding alarm LEDs on the front panel must 

be turned red. 

Restore the loop to full operation. 

Remove the bypass from the safety-related PLC or restore normal operation. 

This test will reveal approximately 99 % of possible Dangerous Undetected failures in the repeater. 

Содержание D1130D

Страница 1: ...D1130 SIL 2 Switch Proximity Detector Repeater Relay Output ISM0048 12 D1130S D1130D INSTRUCTION SAFETY MANUAL SIL 2 Switch Proximity Detector Repeater Relay Output DIN Rail Models D1130S D1130D ...

Страница 2: ...ut 2 5 KV Input switching current levels ON 2 1 mA OFF 1 2 mA switch current 1 65 mA 0 2 mA hysteresis Fault current levels open fault 0 2 mA short fault 6 8 mA when enabled both faults de energize channel relay with dual channel unit D1130D or actuate fault relay with single channel unit D1130S Input equivalent source 8 V 1 KΩ typical 8 V no load 8 mA short circuit Output voltage free SPDT relay ...

Страница 3: ...t Signals SPDT Relay Output for fault detection on single channel version Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 In field programmability by DIP Switch ATEX IECEx UL C UL FM FM C INMETRO EAC EX UKR TR n 898 TÜV Certifications Type Approval Certificate DNV and KR for maritime applications High Reliability SMD components High Density two channels per un...

Страница 4: ...lay Normally Opened NO 2 L Power Supply 115 230 Vac 3 N Power Supply 115 230 Vac 4 Output Ch 2 Common 5 Output Ch 2 Relay Normally Opened NO 6 Output Ch 2 Relay Normally Closed NC 7 Output Ch 1 Relay Normally Closed NC 8 D1130S Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact HAZARDOUS AREA SAFE AREA Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact 13 14 Output Ch 1 A...

Страница 5: ...le Li Li device L cable Li Ri device and L cable R cable IIC Co Ca 2 23 µF Co Ca 15 6 µF Co Ca 69 µF IIB IIC Lo La 172 mH Lo La 689 mH Lo La 1300 mH IIB IIA IIC Lo Ro 930 µH Ω Lo Ro 3720 µH Ω Lo Ro 7440 µH Ω IIB IIA NOTE for USA and Canada IIC equal to Gas Groups A B C D E F and G IIB equal to Gas Groups C D E F and G IIA equal to Gas Groups D E F and G For installations in which both the Ci and L...

Страница 6: ...A ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1130D 13 14 3 L 4 N 8 NC 2 NO 1 COM Supply 115 230 Vac Out 1 In 1 15 16 7 NC 6 NO 5 COM In 2 Out 2 voltage free Contact Proximity Proximity Common positive connection _ voltage free Contact MODEL D1130S 13 14 8 NC 2 NO 1 COM Out 1 A In 1 7 NC 6 NO 5 COM Out 1 B voltage free ...

Страница 7: ... SIL of a certain Safety Function as they are not completely independent one from another Failure rate date taken from Siemens Standard SN29500 Input signal state Pins 13 14 In 1 Ch 1 or 15 16 In 2 Ch 2 Output relay contact state Pins 2 1 Out 1 Ch 1 or 6 5 Out 2 Ch 2 Proximity sensor is OFF or switch is open Open De energize relay Proximity sensor is ON or switch is closed Closed Energized relay I...

Страница 8: ...and channel fault LED Dip switch position 1 2 3 4 ON OFF state ON ON OFF Failure category Failure rates FIT λdd Total Dangerous Detected failures 0 00 λdu Total Dangerous Undetected failures 82 13 λsd Total Safe Detected failures 0 00 λsu Total Safe Undetected failures 203 81 λtot safe Total Failure Rate Safety Function λdd λdu λsd λsu 285 94 MTBF safety function channel 1 1 λtot safe MTTR 8 hours...

Страница 9: ...ized modification must be avoided Warning D1130 Associated Apparatus FM Approved under Entity Concept and non incendive field wiring Unclassified Locations or Hazardous Classified Locations Class I Division 2 Groups A B C D T Code T4 Class I Zone 2 Group IIC IIB IIA T Code T4 FM Approved under Entity Concept or third party approval Hazardous Classified Locations Class I Division 1 Groups A B C D C...

Страница 10: ...50 V 500 VA 80 W resistive load The enclosure provides according to EN60529 an IP20 minimum degree of mechanical protection or similar to NEMA Standard 250 type 1 for indoor installation outdoor installation requires an additional enclosure with higher degree of protection i e IP54 to IP65 or NEMA type 12 13 consistent with the effective operating environment of the specific installation Units mus...

Страница 11: ... 3 Disabled contact proximity sensor Enabled proximity sensor or contact with terminating line resistor ON 13 2 OFF NO 14 1 2 8 NE OR NC 13 14 1 2 8 ND 13 NO 14 1 2 8 NE OR NC 13 14 1 2 8 ND Side A Panel View Input Output Input Output Output Input Output Input CH2 Setting Line fault detection ON IN OUT Operation NO NE or NC ND NO ND or NC NE ON OFF Disabled contact proximity sensor Enabled proximi...

Страница 12: ...ND NE No Fault D1130D Configuration Summary Table Channel IN OUT Operation NO NE or NC ND NO ND or NC NE For SIL applications SW2 OFF SW4 OFF ON 1 2 Channel Line fault detection Disabled contact proximity sensor Enabled For SIL applications proximity sensor or contact with terminating line resistor detects field open circuit and short circuit de energizing output SW1 SW3 1 2 ON OFF OFF ON ON IN OU...

Отзывы: