12 

D1130 

- SIL 2 Switch / Proximity Detector Repeater Relay Output 

G.M. International ISM0048-12 

4

4

1

CH 

Setting 

Line fault 
detection 

IN / OUT 

Operation 

NO-NE or 

NC-ND 

NO-ND or 

NC-NE 

1

4

4

3

3

B Output 

Operation 

Normal 

Parallel 

Mode 

Reverse 

Mode 

OFF 

ON 

Fault 

Output 

ON 

ND 

Mode 

NE 

Mode 

OFF 

ON 

OFF 

Configuration 

Input Output 

Input  Output 

Output 

Input 

Output 

Input 

2

ON 

13 

 

2

OFF 

NO 

14 


NE 

OR 

NC 

13 

14 


ND 

13 

 

NO 

14 


NE 

OR 

NC 

13 

14 


ND 

ON 

OFF 

Disabled 

(contact / proximity sensor) 

Enabled 

(proximity sensor or contact 

with terminating line resistor) 

 

Out B 

Out A 



 

 

 

Out A 


Out B 


No Fault 



NE 

NE 

NE 

ND 

ND 

NE 

No Fault 

D1130D Configuration Summary Table 

Channel 

IN/OUT Operation 

NO-NE or NC-ND 

NO-ND or NC-NE 

(For SIL applications.) 

SW2 

OFF 

SW4 

OFF 

ON 

Channel 

Line fault detection 

Disabled 

(contact/proximity sensor)  

Enabled 

(For SIL applications.) 

(proximity sensor or contact with terminating line resistor, 

detects field open circuit and short circuit de-energizing output) 

SW1 

SW3 

ON 

OFF 

OFF 

ON 

ON 

IN/OUT Operation 

NO-NE or NC-ND 

NO-ND or NC-NE 

(For SIL applications.) 

SW2 

OFF 

ON 

Line fault detection 

Disabled 

Enabled  

(For SIL applications.) 

SW1 

OFF 

ON 

B Output Operation 

Normal  

(For SIL applications.)

 

Fault Output 

SW3 

OFF 

ON 

Mode 

Direct 

Reverse 

ND 

NE 

SW4 

OFF 

ON 

OFF 

ON 

D1130S Configuration Summary Table 

For SIL applications. 

For SIL applications. 

1

2

3

4

ON

CH1

OFF ON OFF OFF

Factory settings 

Dip switch configuration 

D1130S 

For SIL applications. 

Содержание D1130D

Страница 1: ...D1130 SIL 2 Switch Proximity Detector Repeater Relay Output ISM0048 12 D1130S D1130D INSTRUCTION SAFETY MANUAL SIL 2 Switch Proximity Detector Repeater Relay Output DIN Rail Models D1130S D1130D ...

Страница 2: ...ut 2 5 KV Input switching current levels ON 2 1 mA OFF 1 2 mA switch current 1 65 mA 0 2 mA hysteresis Fault current levels open fault 0 2 mA short fault 6 8 mA when enabled both faults de energize channel relay with dual channel unit D1130D or actuate fault relay with single channel unit D1130S Input equivalent source 8 V 1 KΩ typical 8 V no load 8 mA short circuit Output voltage free SPDT relay ...

Страница 3: ...t Signals SPDT Relay Output for fault detection on single channel version Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 In field programmability by DIP Switch ATEX IECEx UL C UL FM FM C INMETRO EAC EX UKR TR n 898 TÜV Certifications Type Approval Certificate DNV and KR for maritime applications High Reliability SMD components High Density two channels per un...

Страница 4: ...lay Normally Opened NO 2 L Power Supply 115 230 Vac 3 N Power Supply 115 230 Vac 4 Output Ch 2 Common 5 Output Ch 2 Relay Normally Opened NO 6 Output Ch 2 Relay Normally Closed NC 7 Output Ch 1 Relay Normally Closed NC 8 D1130S Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact HAZARDOUS AREA SAFE AREA Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact 13 14 Output Ch 1 A...

Страница 5: ...le Li Li device L cable Li Ri device and L cable R cable IIC Co Ca 2 23 µF Co Ca 15 6 µF Co Ca 69 µF IIB IIC Lo La 172 mH Lo La 689 mH Lo La 1300 mH IIB IIA IIC Lo Ro 930 µH Ω Lo Ro 3720 µH Ω Lo Ro 7440 µH Ω IIB IIA NOTE for USA and Canada IIC equal to Gas Groups A B C D E F and G IIB equal to Gas Groups C D E F and G IIA equal to Gas Groups D E F and G For installations in which both the Ci and L...

Страница 6: ...A ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1130D 13 14 3 L 4 N 8 NC 2 NO 1 COM Supply 115 230 Vac Out 1 In 1 15 16 7 NC 6 NO 5 COM In 2 Out 2 voltage free Contact Proximity Proximity Common positive connection _ voltage free Contact MODEL D1130S 13 14 8 NC 2 NO 1 COM Out 1 A In 1 7 NC 6 NO 5 COM Out 1 B voltage free ...

Страница 7: ... SIL of a certain Safety Function as they are not completely independent one from another Failure rate date taken from Siemens Standard SN29500 Input signal state Pins 13 14 In 1 Ch 1 or 15 16 In 2 Ch 2 Output relay contact state Pins 2 1 Out 1 Ch 1 or 6 5 Out 2 Ch 2 Proximity sensor is OFF or switch is open Open De energize relay Proximity sensor is ON or switch is closed Closed Energized relay I...

Страница 8: ...and channel fault LED Dip switch position 1 2 3 4 ON OFF state ON ON OFF Failure category Failure rates FIT λdd Total Dangerous Detected failures 0 00 λdu Total Dangerous Undetected failures 82 13 λsd Total Safe Detected failures 0 00 λsu Total Safe Undetected failures 203 81 λtot safe Total Failure Rate Safety Function λdd λdu λsd λsu 285 94 MTBF safety function channel 1 1 λtot safe MTTR 8 hours...

Страница 9: ...ized modification must be avoided Warning D1130 Associated Apparatus FM Approved under Entity Concept and non incendive field wiring Unclassified Locations or Hazardous Classified Locations Class I Division 2 Groups A B C D T Code T4 Class I Zone 2 Group IIC IIB IIA T Code T4 FM Approved under Entity Concept or third party approval Hazardous Classified Locations Class I Division 1 Groups A B C D C...

Страница 10: ...50 V 500 VA 80 W resistive load The enclosure provides according to EN60529 an IP20 minimum degree of mechanical protection or similar to NEMA Standard 250 type 1 for indoor installation outdoor installation requires an additional enclosure with higher degree of protection i e IP54 to IP65 or NEMA type 12 13 consistent with the effective operating environment of the specific installation Units mus...

Страница 11: ... 3 Disabled contact proximity sensor Enabled proximity sensor or contact with terminating line resistor ON 13 2 OFF NO 14 1 2 8 NE OR NC 13 14 1 2 8 ND 13 NO 14 1 2 8 NE OR NC 13 14 1 2 8 ND Side A Panel View Input Output Input Output Output Input Output Input CH2 Setting Line fault detection ON IN OUT Operation NO NE or NC ND NO ND or NC NE ON OFF Disabled contact proximity sensor Enabled proximi...

Страница 12: ...ND NE No Fault D1130D Configuration Summary Table Channel IN OUT Operation NO NE or NC ND NO ND or NC NE For SIL applications SW2 OFF SW4 OFF ON 1 2 Channel Line fault detection Disabled contact proximity sensor Enabled For SIL applications proximity sensor or contact with terminating line resistor detects field open circuit and short circuit de energizing output SW1 SW3 1 2 ON OFF OFF ON ON IN OU...

Отзывы: