D1130 

- SIL 2 Switch / Proximity Detector Repeater Relay Output 

G.M. International ISM0048-12 

General Description:

 The Switch/Proximity Detector Repeater type D1130 is a DIN Rail unit with one or two independent channels. The unit can be configured for contact or proximity 

detector, NO or NC and for NE or ND SPDT relay output contact. Each channel enables a Safe Area load to be controlled by a switch, or a proximity detector, located in Hazardous Area. 

D1130D dual channel 

type has two independent input channels and actuates the corresponding output relay. Two actuation modes can be independently DIP switch configured on 

each input channel: NO input/NE relay or NO input/ND relay. Contact or proximity sensor and its connection line short or open circuit fault detection is also DIP switch configurable: 

fault detection can be enabled (in case of fault it de-energizes the corresponding output relay and turns the fault LED on) or disabled (in case of fault the corresponding output relay 

repeats the input line open or closed status as configured). 

D1130S single channel 

type has one input channel and two output relays; the unit has two DIP switch configurable operating modes: 

Mode A) input channel actuates in parallel the two output relays (DPDT contact). Relay actuation mode can be independently configured for each output in two modes: NO input/NE 

relay or NO input/ND relay. 

Mode B) input channel actuates output relay A configurable in two modes as in mode A above. Output relay B operates as a fault output (in case of input fault, relay B actuates and the 

fault LED turns on while relay A repeats the input line as configured). 

Actuation can be DIP switch configured in two modes: No input fault/energized relay (it de-energizes in case of fault) or No input fault/de-energized relay (it energizes in case of fault). 

Function:

 1 or 2 channels I.S. switch repeater for contact or EN60947-5-6 proximity. Provides 3 port isolation (input/output/supply). 

Signalling LEDs:

 Power supply indication (green), output status (yellow), line fault (red). 

Field Configurability:

 NO/NC input for contact/proximitor, NE/ND relay operation and fault detection enable/disable. 

EMC: 

Fully compliant with CE marking applicable requirements. 

Supply: 

115-230 Vac, 50-60 Hz nom (85 to 250 Vac, 48 to 400 Hz), ripple within voltage limits 

 10 Vpp; 500 mA time lag fuse and 275 Vrms transient voltage surge suppressor protec-

protected. Limit supply voltage to 250 Vrms for Instrinsic Safety applications. 

Current consumption @ 115 Vac: 

25 mA with short input and relays energized. 

Current consumption @ 230 Vac: 

15 mA with short input and relays energized. 

Max. power consumption: 

at 250 Vac supply voltage, short circuit input and relays energized, 2.0 W for 2 channels D1130D, 1.9 W for 1 channel D1130S. 

Isolation (Test Voltage):

 I.S. In/Out 2.5 KV; I.S. In/Supply 2.5 KV; Out/Supply 2.5 KV; Out/Out 2.5 KV. 

Input switching current levels:

 ON 

 2.1 mA, OFF 

 1.2 mA, switch current 

 1.65 mA ± 0.2 mA hysteresis. 

Fault current levels: 

open fault 

 0.2 mA, short fault 

 6.8 mA 

(when enabled both faults de-energize channel relay with dual channel unit D1130D or actuate fault relay with single channel unit D1130S). 

Input equivalent source: 

8 V 1 K

 typical (8 V no load, 8 mA short circuit). 

Output: 

voltage free SPDT relay contact. 

Contact material: 

AgCdO. 

Contact rating: 

2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load). 

DC Load breaking capacity: 

Mechanical / Electrical life: 

30 * 10

6

 / 1 * 10

5

 operation, typical. 

Operate / Release time: 

7 / 3 ms typical. 

Bounce time NO / NC contact: 

3 / 5 ms. 

Response time: 

20 ms. 

Frequency response: 

10 Hz maximum. 

Compatibility: 

 

CE mark compliant, conforms to Directive: 2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS. 

Environmental conditions: 

Operating: 

temperature limits -20 to + 60 °C, relative humidity max 95 %. 

Storage: 

temperature limits – 45 to + 80 °C. 

Safety Description: 

ATEX:

 II (1)G [Ex ia Ga] IIC, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I, II 3G Ex nAC IIC T4 Gc 

IECEx / INMETRO: 

[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I  

UL: 

AIS / I, II, III / 1 / ABCDEFG, [AEx ia] IIC 

C-UL: 

AIS / I, II, III / 1 / ABCDEFG, [Ex ia] IIC  

FM: 

NI / I / 2 / ABCD / T4, NI / I / 2 / IIC / T4, AIS / I, II, III / 1 / ABCDEFG, AEx [ia] IIC  

FMC: 

NI / I / 2 / ABCD / T4, NI / I / 2 / IIC / T4, AIS / I, II, III / 1 / ABCDEFG, Ex [ia] IIC  

EAC-EX: 

2Ex nA nC [ia Ga] IIC T4 X, [Ex ia Da] IIIC X, [Ex ia Ma] I X. 

UKR TR n. 898:

 2ExnAnCiaIICT4 X, ExiaI X 

associated apparatus and non-sparking electrical equipment. 

Uo/Voc = 10.7 V, Io/Isc = 15 mA, Po/Po = 39 mW at terminals 13-14, 15-16. 

Um = 250 Vrms, -20 °C 

 Ta 

 60 °C. 

Approvals: 

DMT 01 ATEX E 042 X conforms to EN60079-0, EN60079-11, EN60079-26. IECEx BVS 07.0027X conforms to IEC60079-0, IEC60079-11, IEC60079-26 

IMQ 09 ATEX 013 X conforms to EN60079-0, EN60079-15. IECEx IMQ 13.0011X conforms to IEC60079-0, IEC60079-15. 

INMETRO DNV 13.0108 X conforms to ABNT NBR IEC60079-0, ABNT NBR IEC60079-11, ABNT NBR IEC60079-15, ABNT NBR IEC60079-26. 

UL & C-UL E222308 conforms to UL913, UL 60079-0, UL60079-11 for UL and CSA-C22.2 No.157-92, CSA-E60079-0, CSA-E60079-11 for C-UL. 

FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3610, 3611, 3810 and C22.2 No.142, C22.2 No.157, C22.2 No.213, E60079-0, E60079-11, E60079-15. 

C-IT.MH04.B.00306 conforms to GOST R IEC 60079-0,GOST R IEC 60079-11, GOST R IEC 60079-15. 

C

Ц

 16.0034 X conforms to 

ДСТУ

 7113, 

ГОСТ

 22782.5-78, 

ДСТУ

 I

ЕС

 60079-15. 

TUV Certificate No. C-IS-236198-02, SIL 2 according to IEC 61511.  

DNV and KR Type Approval Certificate for maritime applications. 

Mounting: 

T35 DIN Rail according to EN50022. 

Weight:

 

about 145 g D1130D, 140 g D1130S. 

Connection:

 by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm

2

Location:

 Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA 

T4 installation. 

Protection class:

 IP 20. 

Dimensions:

 Width 22.5 mm, Depth 99 mm, Height 114.5 mm. 

 

 

 

Technical Data 

Characteristics 

0.2

0.1

V (V)

I (A)

10

20

30

40

50

100

200

300

0.3 0.5

1

2

5

Resistive 

Load

Содержание D1130D

Страница 1: ...D1130 SIL 2 Switch Proximity Detector Repeater Relay Output ISM0048 12 D1130S D1130D INSTRUCTION SAFETY MANUAL SIL 2 Switch Proximity Detector Repeater Relay Output DIN Rail Models D1130S D1130D ...

Страница 2: ...ut 2 5 KV Input switching current levels ON 2 1 mA OFF 1 2 mA switch current 1 65 mA 0 2 mA hysteresis Fault current levels open fault 0 2 mA short fault 6 8 mA when enabled both faults de energize channel relay with dual channel unit D1130D or actuate fault relay with single channel unit D1130S Input equivalent source 8 V 1 KΩ typical 8 V no load 8 mA short circuit Output voltage free SPDT relay ...

Страница 3: ...t Signals SPDT Relay Output for fault detection on single channel version Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 In field programmability by DIP Switch ATEX IECEx UL C UL FM FM C INMETRO EAC EX UKR TR n 898 TÜV Certifications Type Approval Certificate DNV and KR for maritime applications High Reliability SMD components High Density two channels per un...

Страница 4: ...lay Normally Opened NO 2 L Power Supply 115 230 Vac 3 N Power Supply 115 230 Vac 4 Output Ch 2 Common 5 Output Ch 2 Relay Normally Opened NO 6 Output Ch 2 Relay Normally Closed NC 7 Output Ch 1 Relay Normally Closed NC 8 D1130S Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact HAZARDOUS AREA SAFE AREA Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact 13 14 Output Ch 1 A...

Страница 5: ...le Li Li device L cable Li Ri device and L cable R cable IIC Co Ca 2 23 µF Co Ca 15 6 µF Co Ca 69 µF IIB IIC Lo La 172 mH Lo La 689 mH Lo La 1300 mH IIB IIA IIC Lo Ro 930 µH Ω Lo Ro 3720 µH Ω Lo Ro 7440 µH Ω IIB IIA NOTE for USA and Canada IIC equal to Gas Groups A B C D E F and G IIB equal to Gas Groups C D E F and G IIA equal to Gas Groups D E F and G For installations in which both the Ci and L...

Страница 6: ...A ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1130D 13 14 3 L 4 N 8 NC 2 NO 1 COM Supply 115 230 Vac Out 1 In 1 15 16 7 NC 6 NO 5 COM In 2 Out 2 voltage free Contact Proximity Proximity Common positive connection _ voltage free Contact MODEL D1130S 13 14 8 NC 2 NO 1 COM Out 1 A In 1 7 NC 6 NO 5 COM Out 1 B voltage free ...

Страница 7: ... SIL of a certain Safety Function as they are not completely independent one from another Failure rate date taken from Siemens Standard SN29500 Input signal state Pins 13 14 In 1 Ch 1 or 15 16 In 2 Ch 2 Output relay contact state Pins 2 1 Out 1 Ch 1 or 6 5 Out 2 Ch 2 Proximity sensor is OFF or switch is open Open De energize relay Proximity sensor is ON or switch is closed Closed Energized relay I...

Страница 8: ...and channel fault LED Dip switch position 1 2 3 4 ON OFF state ON ON OFF Failure category Failure rates FIT λdd Total Dangerous Detected failures 0 00 λdu Total Dangerous Undetected failures 82 13 λsd Total Safe Detected failures 0 00 λsu Total Safe Undetected failures 203 81 λtot safe Total Failure Rate Safety Function λdd λdu λsd λsu 285 94 MTBF safety function channel 1 1 λtot safe MTTR 8 hours...

Страница 9: ...ized modification must be avoided Warning D1130 Associated Apparatus FM Approved under Entity Concept and non incendive field wiring Unclassified Locations or Hazardous Classified Locations Class I Division 2 Groups A B C D T Code T4 Class I Zone 2 Group IIC IIB IIA T Code T4 FM Approved under Entity Concept or third party approval Hazardous Classified Locations Class I Division 1 Groups A B C D C...

Страница 10: ...50 V 500 VA 80 W resistive load The enclosure provides according to EN60529 an IP20 minimum degree of mechanical protection or similar to NEMA Standard 250 type 1 for indoor installation outdoor installation requires an additional enclosure with higher degree of protection i e IP54 to IP65 or NEMA type 12 13 consistent with the effective operating environment of the specific installation Units mus...

Страница 11: ... 3 Disabled contact proximity sensor Enabled proximity sensor or contact with terminating line resistor ON 13 2 OFF NO 14 1 2 8 NE OR NC 13 14 1 2 8 ND 13 NO 14 1 2 8 NE OR NC 13 14 1 2 8 ND Side A Panel View Input Output Input Output Output Input Output Input CH2 Setting Line fault detection ON IN OUT Operation NO NE or NC ND NO ND or NC NE ON OFF Disabled contact proximity sensor Enabled proximi...

Страница 12: ...ND NE No Fault D1130D Configuration Summary Table Channel IN OUT Operation NO NE or NC ND NO ND or NC NE For SIL applications SW2 OFF SW4 OFF ON 1 2 Channel Line fault detection Disabled contact proximity sensor Enabled For SIL applications proximity sensor or contact with terminating line resistor detects field open circuit and short circuit de energizing output SW1 SW3 1 2 ON OFF OFF ON ON IN OU...

Отзывы: