D1130 

- SIL 2 Switch / Proximity Detector Repeater Relay Output 

G.M. International ISM0048-12 

Parameters Table 

In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check 
its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded 
by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D1130 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check 
that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective 
gas group. See parameters on

 

enclosure side and the ones indicated in the table below: 

 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Device Parameters 

D1130 Associated 

Apparatus Parameters 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Cable Parameters 

Uo / Voc = 10.7 V 

Ui / Vmax 

D1130 Terminals 

Ch1 

Ch2 

13 -14 

15 -16 

Io / Isc = 15 mA 

Ch1 

Ch2 

13 -14 

15 -16 

Po / Po = 39 mW 

Ch1 

Ch2 

13 -14 

15 -16 

 

Ii/ Imax 

 

Pi / Pi 

 

D1130 Terminals 

Ch1 

Ch2 

13 -14 

15 -16 

Ch1 

Ch2 

13 -14 

15 -16 

Ch1 

Ch2 

13 -14 

15 -16 

D1130 Associated 

Apparatus Parameters 

Ci / Ci  C cable 

 

Li / Li L cable 

 

Li / Ri device and 

L cable / R cable 

 

(IIC) 

Co / Ca = 2.23 µF 
Co / Ca = 15.6 µF 

Co / Ca = 69 µF 

(IIB) 

(IIC) 

Lo / La = 172 mH 
Lo / La = 689 mH 

Lo / La = 1300 mH 

(IIB) 
(IIA) 

(IIC) 

Lo / Ro = 930 µH/

 

Lo / Ro = 3720 µH/

 

Lo / Ro = 7440 µH/

 

(IIB) 
(IIA) 

NOTE for USA and Canada: 

IIC equal to Gas Groups A, B, C, D, E, F and G 
IIB equal to Gas Groups C, D, E, F and G 
IIA equal to Gas Groups D, E, F and G 

For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable), 
then 50 % of Co and Lo parameters are applicable and shall not be exceeded 

(50 % of the Co and Lo become the limits which must include the cable such that 

Ci C cable 

 50 % of Co and Li  L cable 

 50 % of Lo). 

If the cable parameters are unknown, the following value may be used: Capacitance 60pF per foot (180pF per meter), Inductance 0.20µH per foot (0.60µH per meter). 
The Intrinsic Safety Entity Concept allows the interconnection of Intrinsically Safe devices approved with entity parameters not specifically examined in combination as a system 
when the above conditions are respected. 
For Division 1 and Zone 0 installations, the configuration of Intrinsically Safe Equipment must be FM approved under Entity Concept (or third party approved); 
for Division 2 installations, the configuration of Intrinsically Safe Equipment must be FM approved under non-incendive field wiring or Entity Concept (or third party approved). 

Co / Ca = 60 µF 

Co / Ca = 15.6 µF 

(I) 

(IIA) 

(IIIC) 

(I) 

(IIIC) 

Lo / La = 2263 mH 

Lo / La = 689 mH 

Lo / Ro = 12200 µH/

 

Lo / Ro = 3720 µH/

 

(I) 

(IIIC) 

Содержание D1130D

Страница 1: ...D1130 SIL 2 Switch Proximity Detector Repeater Relay Output ISM0048 12 D1130S D1130D INSTRUCTION SAFETY MANUAL SIL 2 Switch Proximity Detector Repeater Relay Output DIN Rail Models D1130S D1130D ...

Страница 2: ...ut 2 5 KV Input switching current levels ON 2 1 mA OFF 1 2 mA switch current 1 65 mA 0 2 mA hysteresis Fault current levels open fault 0 2 mA short fault 6 8 mA when enabled both faults de energize channel relay with dual channel unit D1130D or actuate fault relay with single channel unit D1130S Input equivalent source 8 V 1 KΩ typical 8 V no load 8 mA short circuit Output voltage free SPDT relay ...

Страница 3: ...t Signals SPDT Relay Output for fault detection on single channel version Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 In field programmability by DIP Switch ATEX IECEx UL C UL FM FM C INMETRO EAC EX UKR TR n 898 TÜV Certifications Type Approval Certificate DNV and KR for maritime applications High Reliability SMD components High Density two channels per un...

Страница 4: ...lay Normally Opened NO 2 L Power Supply 115 230 Vac 3 N Power Supply 115 230 Vac 4 Output Ch 2 Common 5 Output Ch 2 Relay Normally Opened NO 6 Output Ch 2 Relay Normally Closed NC 7 Output Ch 1 Relay Normally Closed NC 8 D1130S Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact HAZARDOUS AREA SAFE AREA Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact 13 14 Output Ch 1 A...

Страница 5: ...le Li Li device L cable Li Ri device and L cable R cable IIC Co Ca 2 23 µF Co Ca 15 6 µF Co Ca 69 µF IIB IIC Lo La 172 mH Lo La 689 mH Lo La 1300 mH IIB IIA IIC Lo Ro 930 µH Ω Lo Ro 3720 µH Ω Lo Ro 7440 µH Ω IIB IIA NOTE for USA and Canada IIC equal to Gas Groups A B C D E F and G IIB equal to Gas Groups C D E F and G IIA equal to Gas Groups D E F and G For installations in which both the Ci and L...

Страница 6: ...A ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1130D 13 14 3 L 4 N 8 NC 2 NO 1 COM Supply 115 230 Vac Out 1 In 1 15 16 7 NC 6 NO 5 COM In 2 Out 2 voltage free Contact Proximity Proximity Common positive connection _ voltage free Contact MODEL D1130S 13 14 8 NC 2 NO 1 COM Out 1 A In 1 7 NC 6 NO 5 COM Out 1 B voltage free ...

Страница 7: ... SIL of a certain Safety Function as they are not completely independent one from another Failure rate date taken from Siemens Standard SN29500 Input signal state Pins 13 14 In 1 Ch 1 or 15 16 In 2 Ch 2 Output relay contact state Pins 2 1 Out 1 Ch 1 or 6 5 Out 2 Ch 2 Proximity sensor is OFF or switch is open Open De energize relay Proximity sensor is ON or switch is closed Closed Energized relay I...

Страница 8: ...and channel fault LED Dip switch position 1 2 3 4 ON OFF state ON ON OFF Failure category Failure rates FIT λdd Total Dangerous Detected failures 0 00 λdu Total Dangerous Undetected failures 82 13 λsd Total Safe Detected failures 0 00 λsu Total Safe Undetected failures 203 81 λtot safe Total Failure Rate Safety Function λdd λdu λsd λsu 285 94 MTBF safety function channel 1 1 λtot safe MTTR 8 hours...

Страница 9: ...ized modification must be avoided Warning D1130 Associated Apparatus FM Approved under Entity Concept and non incendive field wiring Unclassified Locations or Hazardous Classified Locations Class I Division 2 Groups A B C D T Code T4 Class I Zone 2 Group IIC IIB IIA T Code T4 FM Approved under Entity Concept or third party approval Hazardous Classified Locations Class I Division 1 Groups A B C D C...

Страница 10: ...50 V 500 VA 80 W resistive load The enclosure provides according to EN60529 an IP20 minimum degree of mechanical protection or similar to NEMA Standard 250 type 1 for indoor installation outdoor installation requires an additional enclosure with higher degree of protection i e IP54 to IP65 or NEMA type 12 13 consistent with the effective operating environment of the specific installation Units mus...

Страница 11: ... 3 Disabled contact proximity sensor Enabled proximity sensor or contact with terminating line resistor ON 13 2 OFF NO 14 1 2 8 NE OR NC 13 14 1 2 8 ND 13 NO 14 1 2 8 NE OR NC 13 14 1 2 8 ND Side A Panel View Input Output Input Output Output Input Output Input CH2 Setting Line fault detection ON IN OUT Operation NO NE or NC ND NO ND or NC NE ON OFF Disabled contact proximity sensor Enabled proximi...

Страница 12: ...ND NE No Fault D1130D Configuration Summary Table Channel IN OUT Operation NO NE or NC ND NO ND or NC NE For SIL applications SW2 OFF SW4 OFF ON 1 2 Channel Line fault detection Disabled contact proximity sensor Enabled For SIL applications proximity sensor or contact with terminating line resistor detects field open circuit and short circuit de energizing output SW1 SW3 1 2 ON OFF OFF ON ON IN OU...

Отзывы: