6 Instructions for Use

Hand the Instructions for Use to the user and instruct in the safe
and economical use of the fire front and back boiler.

Advise the customer that they should read their Users
instructions before operating the fire and always follow the
advice in the Section headed “Cleaning your Fire”.

Advise that any smell which may be apparent on initial lighting
is quite normal and it will quickly disappear.

Advise that the fire front is fitted with a flue blockage safety
device, and refer to the Instructions for Use.

Important.  Advise that soft wall coverings, for example, blown
vinyl wallpaper, are easily affected by heat, they may, therefore,
scorch or become discoloured when close to a heating appliance.
This should be borne in mind when having a heating appliance
installed and when redecorating.

Advise the user that, to ensure the continued efficient and safe
operation of the appliance it is recommended that it is checked
and serviced at regular intervals.

The frequency of servicing

will depend upon the particular installation and usage, but in
general once a year should be enough.

Draw attention, if applicable. to the current issue of the Gas
Safety (Installation and Use) Regulations, Section 35, which
imposes a duty of care on all persons who let out any property
containing a gas appliance.

It is the Law that any servicing is carried out by a competent
person.

Refer to the Instructions for Use and show how to light the fire
front, in the event of an ignition system failure, with a spill or long
match

Advise the user of the precautions necessary  to prevent
damage to the system, boiler and the building, in the event of
the heating system being out of use during frost or freezing
conditions.

Reminder, leave these instructions with the user.

Diagram 6.1

5094

SPILL

BURNER

SPILL

3 Flue Systems

7 Servicing

Notes

To ensure the continued efficient and safe operation of the
appliance it is recommended that it is checked and serviced at
regular intervals.  The frequency of servicing will depend upon
the particular installation and usage, but in general once a year
should be enough.

It is the Law that servicing is carried out by a competent person.

Make sure that the fire is cold before carrying out any servicing.

After servicing, or replacing parts, always test for gas soundness
with a suitable leak detection fluid.  To test the gas tap, refix the
fire front and apply leak detection fluid to all joints, replace the
glass panel, light the burner and visually check all joints for
leakage whilst changing tap settings.

Carry out functional check on controls, see Section 4 and 5.

Other than for replacing the glass panel, internal fire front parts
and lighting the fire front should be removed from its fixings by
reversing the instructions in Section 4 and 5.  Make sure that
the side panels and feet are removed.  Refit controls cover plinth
so that the fire can stand upright.

Unless stated otherwise reassembly all parts in the reverse
order to removal.

The back boiler should be serviced at this time, refer to Back
Boiler Installation and Servicing Instructions.

The flue blockage safety device MUST NOT be adjusted or
disconnected.  If replacing use only the correct and approved
parts.

7.1 Glass Panel

Lift canopy off, take care as it is made of cast iron.

Swing open side panels to their stops, about 5mm, as diagram
7 & 18 (Instructions for Use).

To remove the glass panel, refer to diagram 3.3.

7.2 Internal Fire Front Parts

Remove internal fire front parts as diagrams 15 to 11. (Instructions
for Use).

Remove bottom plate, see diagram 5.3.

Examine these parts and replace as necessary.

7.3 Burner and Injectors

Remove the front castings, see diagram 5.6.

Remove the lower front baffle, see diagram 7.1.

Remove the burner baffle, see diagram 7.1.

Remove the RH. leg, see diagram 5.4.

Remove the side castings, see diagram 5.5.

Advise the user that  the ‘Benchmark’ logbook should be
completed by the installation engineer on completion of
commissioning or servicing.

Содержание SAXONY 2 BBU FIRE FRONT

Страница 1: ...ervice number 01773 828100 Our Guarantee gives you peace of mind plus valuable protection against breakdown by covering the cost of Guarantee Registration BBU Fire Front For use with a specially desig...

Страница 2: ...hich are man made vitreous silicate fibres Excessive exposure to these materials may cause temporary irritation to eyes skin and respiratory tract consequently it makes sense to take care when handlin...

Страница 3: ...panel is broken or missing WARNING The glass panel gets very hot when the fire front is on and MUST NOT be touched The glass panel does not provide full protection for the young elderly or infirm In...

Страница 4: ...um double pole contact separation of 3mm serving only the appliance and system controls Thecoloursofthreecoreflexiblecableare blue neutral brown live green and yellow earth As the markings on your plu...

Страница 5: ...ghting procedure only now keep the control knob A pushed in for a little longer than before after the pilot has lit Note Always wait three minutes before attempting to relight the pilot after it has g...

Страница 6: ...turn the tap fully clockwise to O position and release If there is a visible build up of soot on the fuel effect pieces follow the instructions in Section on Cleaning the Fire Lighting the Fire Front...

Страница 7: ...s fire front When replacing fit as shown in diagrams 9 to 16 Note Each fuel effect piece is numbered on its back DO NOT USE MORE FUEL EFFECT PIECES THAN SHOWN To Replace the Battery The battery suppli...

Страница 8: ...CT PIECE MUST SIT ON SUPPORT ANGLE NOTE NOTE FUEL EFFECT PIECE MUST SIT ON SUPPORT ANGLE FUEL EFFECT PIECE MUST SIT ON SUPPORT ANGLE NOTE FUEL EFFECT PIECE POSITION 4 SUPPORT ANGLE FOR FUEL EFFECT PIE...

Страница 9: ...s of fuel effect pieces 4 and 5 are seated on flat areas of fuel effect pieces 1 2 and 3 COMPLETED FUEL EFFECT BED Diagram 17 CANOPY LOCATING PIN LOCATING HOLE 4850 3943 S Diagram 19 5283 SECURING SCR...

Страница 10: ...tton D until pilot burner E lighted Look at flame through viewing window F At initial lighting of the boiler air may be present and several attempts may be needed to light the pilot Keep control knob...

Страница 11: ...with a flue blockage safety device which will shut down the fire if there is an unacceptable spillage of products at the draught diverter If the fire front shuts down frequently for no appreant reason...

Страница 12: ...back boiler must be correctly positioned in the builder s opening as the fire front is located by connection to it The back boiler air duct acts as a support for the fire front The top of the fire fr...

Страница 13: ...face area of the surround must be removed see diagram 2 3 This area to the depth removed should then be rendered with a sand cement mixture 2 3 Without Surround or Hearth The fire front fixing wall f...

Страница 14: ...TTOM PLATE FLUE SPIGOT FIRE BODY ASSEMBLY WALL SEALING PLATE L H SIDE CASTING FUEL EFFECT BED LITERATURE L H SIDE PANEL CANOPY FRONT CASTING PLINTH REAR SUPPORT LEGS 2 R H SIDE PANEL R H SIDE CASTING...

Страница 15: ...x 11 2 PLATE FIXING G WALL WALL SEALING PLUG PLATE FIXING SCREW UPPER SIDE RETAINING 3 Fire Front Preperation KEY Diagram 3 2 J SCREW FLUE SPIGOT FIXING No 8x3 8 in K SCREW SENSING TUBE M4x10 FIXING...

Страница 16: ...spare 3 3 Gas Supply Tube and Sensing Tubes Preparation Remove the plastic ferrule from the bulkhead connector on the air duct and discard Fixtheflaredendofthebackboilersensingtubetothebulkhead conne...

Страница 17: ...ts the length of pipe that requires cutting off P C C GAS FIRE SUPPLY TUBE FIRE FIXING WALL FACE Diagram 3 6 5245 GAS SERVICE COCK UNION Firefront sensing tube Shorten the plain end of the fire front...

Страница 18: ...screw up but leave sufficient screw thread proud to accept the fire front Note If the fire front fixing wall face is not of a solid construction to a minimum depth of 40mm for example hollow brick or...

Страница 19: ...s Connection Place the tubing nut and olive from the loose items pack onto the prepared end of the gas supply tube see diagram 4 8 Connect the gas supply as diagram 4 8 tighten the nut and olive at th...

Страница 20: ...SECURING SCREW STOP LOCATING PIN AND HOLE LOCATING PIN AND HOLE L H SIDE PANEL R H SIDE PANEL R H SIDE PANEL GAS CONTROL KNOB LOCATING PIN AND HOLE J J 4849 Diagram 4 7 TUBE NUT SENSING TUBE TUBE NUT...

Страница 21: ...hin three seconds release the tap wait ten seconds and repeat the lighting operation Push the control knob fully in and turn it anti clockwise to 1 ignition see diagram 5 2 clicking of the ignition wi...

Страница 22: ...arallel to the side panels This adjustment can be done when the canopy is in place 5 4 Fitting of Plinth Before fitting the plinth please read the instructions on it Fit the plinth onto the guides and...

Страница 23: ...1 FRONT SECURING SCREW 2 L 7457 BOTTOM PLATE Diagram 5 3 5071 SECURING SCREW 2 LEVELLING SCREW WASHER Diagram 5 4 5073 F A 4848 Diagram 5 6 LOCATION PIN VIEWED FROM REAR FRONT CASING LOCATION SLOT Di...

Страница 24: ...drawn into the fire front draught diverter and boiler draught diverter If spillage occurs leave the back boiler alight for up to a further five minutes and repeat tests Leave the back boiler alight N...

Страница 25: ...tinued efficient and safe operation of the appliance it is recommended that it is checked and serviced at regular intervals The frequency of servicing will depend upon the particular installation and...

Страница 26: ...7 5 Ignition Lead Remove the burner refer to Section 7 3 Disconnectthetubenuts removethemountingbracketsecuring screws and flue blockage safety device see diagram 7 6 Check the ignition lead see diag...

Страница 27: ...TION UNION CONNECTION 7 Servicing Diagram 7 5 INJECTORS INJECTOR BOX COVER PULL FORWARDS BURNER Diagram 7 4 5172 Diagram 7 3 3958 S SECURING SCREW NOTE Chamfered edge to be on this side UNION CONNECTI...

Страница 28: ...NTING BRACKET SECURING SCREW ELECTRICAL CONNECTIONS MICRO SWITCH SECURING SCREW 2 INSULATION MICRO SWITCH INSULATION NUT 2 GAS TAP MOUNTING BRACKET 3960 S 5248 Diagram 7 7 EARTH POST ELECTRODE 18 67 E...

Страница 29: ...20 6677 29 221648B 7 Servicing Diagram 7 9 THERMOCOUPLE NUT Diagram 7 10 Diagram 7 11 5 7 9 GAS TAP SECURING SCREWS GAS TAP BODY PLUG O RING WASHER SPRING GAS TAP BRACKET AND NITING PLATE ASSEMBLY SEC...

Страница 30: ...rialwiringdiagram 8 1 8 3 Thermocouple To test a thermocouple a meter with a range of 0 to 30mV is required together with a thermocouple interrupter test unit similar to the British Gas Minitest 6 uni...

Страница 31: ...connector within 4mm of burner and turn tap to energise igniter Is there a spark at the gap Remove ignition lead from ignition unit and place screw driver between appliance chassis earth and ignition...

Страница 32: ...in ignition position Ignite burner allowing thermocouple to attain operating temperature Measure the OPEN CIRCUIT voltage Is voltage greater than 15mV Faulty thermocouple Replace flue blockage safety...

Страница 33: ...ut see diagram 7 10 Remove the ignition lead see diagram 19 Instructions for Use Note When refitting the flue blockage safety device take care not to trap the ignition lead under the mounting bracket...

Страница 34: ...3 WW4617 312 997 Ignition lead 14 448103 135 925 Gas tap control knob 15 800449 136 927 Gas tap 16 202179 152 949 Spark generator 17 208673 162 208 Filter Key No Part No Part No G C Description GAS TA...

Страница 35: ...Supplied By www heating spares co Tel 0161 620 6677 35 221648B 9 Replacement Parts Diagram 9 2 7 1 6 4 2 3 5 9 8 13 5092 10 16 12 14 15 17...

Страница 36: ...set in diagram 20 Instructions for Use If one is fitted this supplement MUST be ignored 10 1 General TofitthefirefronttooneoftheaboveEXISTINGGLOW WORM BACK BOILER UNITS follow the instructions below 1...

Отзывы: