3 Fire Front Preperation

3.1 Unpacking

The fire front is delivered in two packs, one contains the body
assembly, fuel effect pieces and supply tube pack.

The other contains the fire front castings, side panels, plinth and
loose items pack.  Refer to diagram 3.1. to identify the parts.

To unpack carton 1, lift out the top fitting containing the fire
spigot and combustion chamber bottom plate, lift out the
cardboard front fitting, the supply tube pack and the two boxes
containing the fuel effect pieces.

Lift the outer carton clear to leave the fire front sitting in the base
tray.

To unpack carton 2, lift out the cardboard tray containing the
plinth and side panels.  Lift out the loose items pack, legs box
and canopy.  Remove the internal cardboard fitting and lift out
the lower front and side castings.

Put these items on one side until required.  Check contents of
loose items pack against list.

Remove the glass front panel, see diagram 3.3.

It is suggested that the side extensions, from the castings pack,
be fitted at this time to the left and right hand side panels.

NOTE: These are a slide fit onto the louvres.

3.2 Flue Spigot Assembly

Note.  This is marked “Homeglow BBU”

Leave the fire front sitting in the base tray.

Remove the two plastic transit studs securing the wall sealing
plate to the rear of the fire front and put it on one side until
required.

Secure the spigot  assembly to the fire front back with the self
taping screws provided, in the loose items pack, see diagram
3.4.

Note.  There are eight self tapping screws in the pack, one
spare.

3.3 Gas Supply Tube and Sensing Tubes

Preparation

Remove the plastic ferrule from the bulkhead connector on the
air duct and discard.

Fix the flared end of the back boiler sensing tube to the bulkhead
connection on the boiler air duct with the tubing nut provided.
Slide the sensing tube mounting bracket assembly over the
back boiler sensing tube and fix to the casing with the screw
provided, see diagram 4.1.  Fit the sensing tube filter onto the
fitting assembly, see diagram 4.1. Take care not to damage the
filter.

Important.  Make sure that the mounting bracket assembly is
pushed back to the fire front face of the boiler casting and check
3mm distance is achieved and the back boiler sensing tube
does not extend above the sensing tube bracket assembly, see
diagram 4.1.

Note. After fitting the flue blockage safety device sensing  tube
please refer to the 'commisioning' section of the back boiler unit
and relight the boiler to test the device.

Check that the gas service cock is in the Off position, see
diagram 3.5.

The inlet supply tube, back boiler sensing tube assembly and
fire front sensing tube are packed in the supply tube pack, see
diagram 3.2.

This supply tube and fire front sensing tube may need to be cut,
at the plain end, dependent on the model and position of the
back boiler in the opening.

Diagram 3.3

GLASS RETAINING
BRACKET

GLASS 
FRONT PANEL

4844

Diagram 3.4

FLUE SPIGOT ASSEMBLY

SECURING
SCREW (7)

J

3923 S

Gas Supply Tube

Measure the distance “C”, see diagram 3.6, from the front mark
“P” on the air duct to the fire front fixing wall face.

Use a straight edge across the opening.

Shorten the plain end of the gas supply tube by the distance “C”.
No shortening is required when mark “P” is level with the fire
front fixing wall face, “C” being zero.

The maximum distance for “C” will be 67mm (2

5

/

8

in).

Содержание SAXONY 2 BBU FIRE FRONT

Страница 1: ...ervice number 01773 828100 Our Guarantee gives you peace of mind plus valuable protection against breakdown by covering the cost of Guarantee Registration BBU Fire Front For use with a specially desig...

Страница 2: ...hich are man made vitreous silicate fibres Excessive exposure to these materials may cause temporary irritation to eyes skin and respiratory tract consequently it makes sense to take care when handlin...

Страница 3: ...panel is broken or missing WARNING The glass panel gets very hot when the fire front is on and MUST NOT be touched The glass panel does not provide full protection for the young elderly or infirm In...

Страница 4: ...um double pole contact separation of 3mm serving only the appliance and system controls Thecoloursofthreecoreflexiblecableare blue neutral brown live green and yellow earth As the markings on your plu...

Страница 5: ...ghting procedure only now keep the control knob A pushed in for a little longer than before after the pilot has lit Note Always wait three minutes before attempting to relight the pilot after it has g...

Страница 6: ...turn the tap fully clockwise to O position and release If there is a visible build up of soot on the fuel effect pieces follow the instructions in Section on Cleaning the Fire Lighting the Fire Front...

Страница 7: ...s fire front When replacing fit as shown in diagrams 9 to 16 Note Each fuel effect piece is numbered on its back DO NOT USE MORE FUEL EFFECT PIECES THAN SHOWN To Replace the Battery The battery suppli...

Страница 8: ...CT PIECE MUST SIT ON SUPPORT ANGLE NOTE NOTE FUEL EFFECT PIECE MUST SIT ON SUPPORT ANGLE FUEL EFFECT PIECE MUST SIT ON SUPPORT ANGLE NOTE FUEL EFFECT PIECE POSITION 4 SUPPORT ANGLE FOR FUEL EFFECT PIE...

Страница 9: ...s of fuel effect pieces 4 and 5 are seated on flat areas of fuel effect pieces 1 2 and 3 COMPLETED FUEL EFFECT BED Diagram 17 CANOPY LOCATING PIN LOCATING HOLE 4850 3943 S Diagram 19 5283 SECURING SCR...

Страница 10: ...tton D until pilot burner E lighted Look at flame through viewing window F At initial lighting of the boiler air may be present and several attempts may be needed to light the pilot Keep control knob...

Страница 11: ...with a flue blockage safety device which will shut down the fire if there is an unacceptable spillage of products at the draught diverter If the fire front shuts down frequently for no appreant reason...

Страница 12: ...back boiler must be correctly positioned in the builder s opening as the fire front is located by connection to it The back boiler air duct acts as a support for the fire front The top of the fire fr...

Страница 13: ...face area of the surround must be removed see diagram 2 3 This area to the depth removed should then be rendered with a sand cement mixture 2 3 Without Surround or Hearth The fire front fixing wall f...

Страница 14: ...TTOM PLATE FLUE SPIGOT FIRE BODY ASSEMBLY WALL SEALING PLATE L H SIDE CASTING FUEL EFFECT BED LITERATURE L H SIDE PANEL CANOPY FRONT CASTING PLINTH REAR SUPPORT LEGS 2 R H SIDE PANEL R H SIDE CASTING...

Страница 15: ...x 11 2 PLATE FIXING G WALL WALL SEALING PLUG PLATE FIXING SCREW UPPER SIDE RETAINING 3 Fire Front Preperation KEY Diagram 3 2 J SCREW FLUE SPIGOT FIXING No 8x3 8 in K SCREW SENSING TUBE M4x10 FIXING...

Страница 16: ...spare 3 3 Gas Supply Tube and Sensing Tubes Preparation Remove the plastic ferrule from the bulkhead connector on the air duct and discard Fixtheflaredendofthebackboilersensingtubetothebulkhead conne...

Страница 17: ...ts the length of pipe that requires cutting off P C C GAS FIRE SUPPLY TUBE FIRE FIXING WALL FACE Diagram 3 6 5245 GAS SERVICE COCK UNION Firefront sensing tube Shorten the plain end of the fire front...

Страница 18: ...screw up but leave sufficient screw thread proud to accept the fire front Note If the fire front fixing wall face is not of a solid construction to a minimum depth of 40mm for example hollow brick or...

Страница 19: ...s Connection Place the tubing nut and olive from the loose items pack onto the prepared end of the gas supply tube see diagram 4 8 Connect the gas supply as diagram 4 8 tighten the nut and olive at th...

Страница 20: ...SECURING SCREW STOP LOCATING PIN AND HOLE LOCATING PIN AND HOLE L H SIDE PANEL R H SIDE PANEL R H SIDE PANEL GAS CONTROL KNOB LOCATING PIN AND HOLE J J 4849 Diagram 4 7 TUBE NUT SENSING TUBE TUBE NUT...

Страница 21: ...hin three seconds release the tap wait ten seconds and repeat the lighting operation Push the control knob fully in and turn it anti clockwise to 1 ignition see diagram 5 2 clicking of the ignition wi...

Страница 22: ...arallel to the side panels This adjustment can be done when the canopy is in place 5 4 Fitting of Plinth Before fitting the plinth please read the instructions on it Fit the plinth onto the guides and...

Страница 23: ...1 FRONT SECURING SCREW 2 L 7457 BOTTOM PLATE Diagram 5 3 5071 SECURING SCREW 2 LEVELLING SCREW WASHER Diagram 5 4 5073 F A 4848 Diagram 5 6 LOCATION PIN VIEWED FROM REAR FRONT CASING LOCATION SLOT Di...

Страница 24: ...drawn into the fire front draught diverter and boiler draught diverter If spillage occurs leave the back boiler alight for up to a further five minutes and repeat tests Leave the back boiler alight N...

Страница 25: ...tinued efficient and safe operation of the appliance it is recommended that it is checked and serviced at regular intervals The frequency of servicing will depend upon the particular installation and...

Страница 26: ...7 5 Ignition Lead Remove the burner refer to Section 7 3 Disconnectthetubenuts removethemountingbracketsecuring screws and flue blockage safety device see diagram 7 6 Check the ignition lead see diag...

Страница 27: ...TION UNION CONNECTION 7 Servicing Diagram 7 5 INJECTORS INJECTOR BOX COVER PULL FORWARDS BURNER Diagram 7 4 5172 Diagram 7 3 3958 S SECURING SCREW NOTE Chamfered edge to be on this side UNION CONNECTI...

Страница 28: ...NTING BRACKET SECURING SCREW ELECTRICAL CONNECTIONS MICRO SWITCH SECURING SCREW 2 INSULATION MICRO SWITCH INSULATION NUT 2 GAS TAP MOUNTING BRACKET 3960 S 5248 Diagram 7 7 EARTH POST ELECTRODE 18 67 E...

Страница 29: ...20 6677 29 221648B 7 Servicing Diagram 7 9 THERMOCOUPLE NUT Diagram 7 10 Diagram 7 11 5 7 9 GAS TAP SECURING SCREWS GAS TAP BODY PLUG O RING WASHER SPRING GAS TAP BRACKET AND NITING PLATE ASSEMBLY SEC...

Страница 30: ...rialwiringdiagram 8 1 8 3 Thermocouple To test a thermocouple a meter with a range of 0 to 30mV is required together with a thermocouple interrupter test unit similar to the British Gas Minitest 6 uni...

Страница 31: ...connector within 4mm of burner and turn tap to energise igniter Is there a spark at the gap Remove ignition lead from ignition unit and place screw driver between appliance chassis earth and ignition...

Страница 32: ...in ignition position Ignite burner allowing thermocouple to attain operating temperature Measure the OPEN CIRCUIT voltage Is voltage greater than 15mV Faulty thermocouple Replace flue blockage safety...

Страница 33: ...ut see diagram 7 10 Remove the ignition lead see diagram 19 Instructions for Use Note When refitting the flue blockage safety device take care not to trap the ignition lead under the mounting bracket...

Страница 34: ...3 WW4617 312 997 Ignition lead 14 448103 135 925 Gas tap control knob 15 800449 136 927 Gas tap 16 202179 152 949 Spark generator 17 208673 162 208 Filter Key No Part No Part No G C Description GAS TA...

Страница 35: ...Supplied By www heating spares co Tel 0161 620 6677 35 221648B 9 Replacement Parts Diagram 9 2 7 1 6 4 2 3 5 9 8 13 5092 10 16 12 14 15 17...

Страница 36: ...set in diagram 20 Instructions for Use If one is fitted this supplement MUST be ignored 10 1 General TofitthefirefronttooneoftheaboveEXISTINGGLOW WORM BACK BOILER UNITS follow the instructions below 1...

Отзывы: