5 Lighting, Testing and Fitting Internal Parts
10
10
10
DIVERTER
PLATE
FIRE SPIGOT NOT
SHOWN FOR CLARITY
560 SMOKE
MATCH
EXTENSION
FRONT VIEW
SIDE VIEW
TORCH
25 mm
25 mm
MATCH EXTENSION
L.H. SIDE
PANEL
DRAUGHT
DIVERTER
SMOKE MATCH
EXTENSION
Diagram 5.8
Diagram 5.9
5169
5168
Test Where No Fan is Present
Close all outside doors and windows in the room where the
appliance is installed.
Light the fire front only and set tap position to 4. After five
minutes apply a spillage test as shown in diagram 5.8 and 5.9.
During tests smoke should be drawn into the fire draught
diverter and the boiler draught diverter.
If spillage occurs, leave the fire front alight for up to a further ten
minutes and repeat test. Turn the fire front burner off.
Next light the back boiler only. After ten minutes apply spillage
test as shown in diagram 5.8 and 5.9. During tests smoke
should be drawn into the fire front draught diverter and boiler
draught diverter.
If spillage occurs, leave the back boiler alight for up to a further
five minutes and repeat tests.
Leave the back boiler alight.
Now light the fire front. After ten minutes apply spillage tests as
shown in diagram 5.8 and 5.9. During tests smoke should be
drawn into the fire draught diverter and boiler draught diverter.
If spillage occurs leave back boiler and fire front alight for up to
a further five minutes and repeat tests.
Test Where a Fan is Present
A fan means an extract fan or a fan for other open flued
appliances or a circulating fan for a warm air unit, whether or not
gas fired. With the fan switched off carryout the appropriate
spillage test with all doors and windows closed, as above.
If the above spillage test is satisfactory carry on as follows:
Open all doors connecting the room containing the appliance
and the room in which the fan is fitted.
Close all other doors and windows in the premises.
If the fan is in the same room as the appliance, close all doors
and windows in that room.
Switch the fan on and repeat the spillage test as above.